0 0 <br /> SAN JOAQUIN COUNTY <br /> ENVIRONMENTAL HEALTH DEPARTMENT <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sigov.org/ehd <br /> UNDERGROUND STORAGE TANK(UST) PROGRAM INSPECTION REPORT CONTINUED <br /> FacilitName: COS Municipal Service Center Facility : 1465 S. Lincoln St. Stockton, CA Dae: Apr 16, 2014 <br /> VIOLATIONS <br /> # C1 C2 M Code Section HSC=CA Health and safetyCode;CFR=Code of Federal Regulations <br /> C1=Class 1 violation;C2=Class 2 violation;M=Minor violation <br /> Non-Pressurized Piping(continued) <br /> 702 CCR 2643(e) Biennial tightness test of gravity piping not performed(pre-January 1,1984) (M1) <br /> 703 CCR 2643(d) Triennial line test for conventional suction piping not performed(pre-January 1,1984) (Mill <br /> Other Violations <br /> 999 Other: See attached"Continuation—Official Inspection Report"for violation(s)not listed above. <br /> SUMMARY OF VIOLATIONS <br /> (CLASS 1,CLASS 11,or MINOR-Notice to Comply) <br /> On site to witness the annual monitoring system certification testing and conduct the routine inspection. <br /> 104. Current financial responsibility documents have not been submitted to the EHD. The most recent <br /> copy submitted to EHD was valid until 4-15-14. Current financial responsibility documents are required <br /> to be submitted annually. Immediately submit a copy of the financial responsibility documents to the <br /> EHD. Alternatively, log into CERS, upload the required information, and submit for review by the EHD. <br /> Complete by 5-16-14. <br /> 201. Maintenance records for the L4 87 annular alarms on 8-16-13 and 6-30-13 were not found on site <br /> nor did the designated operator document what was done in response to these alarms. These records <br /> shall be kept on site for at least 3 years. Ensure that maintenance records for alarms are kept on site. <br /> 204. The designated operator failed to document responses to the alarms from the attached alarm <br /> history on the 8-28-13 and 7-29-13 designated operator monthly inspection reports. The missing alarms <br /> include: 8-16-13 and 6-30-13 L4 87 annular sensor alarms. The 5-29-13 designated operator report did <br /> not have attached a copy of the alarm history. During the monthly inspection, the designated operator <br /> shall review the alarm history for the previous month, check that each alarm was documented and <br /> responded to appropriately, and attach a copy of the alarm history with documentation taken in response <br /> to any alarms to the monthly report. Ensure that designated operators performing monthly inspections <br /> at this facility are including all of the required information on the reports. <br /> 303. Approximately one cup of liquid is at the eastern bottom of the 87 piping sump. The 87 piping <br /> sump sensor was located above the liquid in the sump approximately one inch above the lowest point of <br /> the sump and not located to detect a leak at the earliest opportunity. Monitoring equipment shall be <br /> maintained to be able to detect a leak at the earliest possible opportunity. During the inspection, the <br /> technician adjusted the hanger of the sensor and repositioned the sensor so that it reaches the lowest <br /> point of the sump to detect a leak at the earliest opportunity. Continue to ensure that all sensors are <br /> properly positioned to detect a leak at the earliest opportunity. <br /> ALL EHD STAFF TIME ASSOCIATED WITH FAILING TO COMPLY BY THE ABOVE NOTED DATES WILL BE BILLED AT THE CURRENT HOURLY RATE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Inspector Received RN Title:_ �n <br /> EHD 23-02 Rev 04/19/12 P e3 UST I PECTION REPORT <br />