Laserfiche WebLink
0812712012 15:50 (209) 465-4988 Henderson Maintenance Cc <br />Page 718 <br />SWRCB, January 2002 <br />Page of 7 <br />9. SP=OVERVUL CONTAIN NT BOUS <br />Facility is Not E ipplq With SpilUOverfill Containment Boxes fl <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />0 Spill Bucket Manufacturer ®industry Standard fl Professional Engineer <br />fl Other (Specify) <br />Test Method Used: <br />fl Pressure D Vacuum ®Hydrostatic <br />fl Other (Specify) <br />Test Equipment Used: WATER, TAPE MEASURE <br />Equipment Resolution: 1116' <br />Spill Box #87 FILL Spill Box # 87 <br />Spill Box # DSL Spill Box # <br />VAPOR <br />FILL <br />Bucket Diameter: <br />I2" 12" <br />12" <br />Bucket Depth: <br />14" 13.5" <br />16.75" <br />Wait time between applying <br />pmssure/vacuum/water and <br />5 MIN 5 MIN <br />5 MIN <br />starting test: <br />Test Start Time: <br />0936 0936 <br />1245 <br />initial Reading <br />13.5" 12.5" <br />16' <br />Test End Time: <br />1.036 1036 <br />.1345 <br />Final Reading (RF} <br />13.5" 125" <br />164 <br />Test Duration: <br />l HR I HR <br />1 HR <br />Change in Reading (RF-Ri): <br />0 0 <br />0 <br />Pass/Fail Thnshold or <br />0 0 <br />0 <br />Criteria: <br />Test Result: 1 <br />0 Pass fl Fail®Pass fl Fail <br />@Pass ❑ Fail 1 fl Pan ❑ Fail <br />Comments — (include information on re s made prior to test� and recommenlded&tiow-up fors{aited tests) <br />