SPILL CONTAINER TEST REPORT <br />TEST DATE: July 22, 2011 <br />1. OWNER <br />Name Quik Stop Markets, Inc. <br />Address 4567 Enterprise Street Fremont, CA 94538 Phone # 510-657-8500 <br />Contact Michael Karvelot <br />2. FACILITY <br />Name Quik Stop Market #152 <br />Address 1721 S. Cherokee Lane #1 Lodi, CA 95240 Phone # 510-657-8500 <br />Contact Michael Karvelot <br />3. CUPA <br />Name San Joaquin County Environmental Health Notified July 15, 2011 <br />Address 600 E. Main Street Stockton, CA 95202 Phone # 209-468-8257 <br />Contact Aris Cacapit Fax # 209-468-3433 <br />Inspector Present Aris caca it <br />4. TESTING CONTRACTOR <br />Name Walton Engineering, Inc. Lic# 617238 A, B, Haz <br />Address P.O. Box 1025, West Sacramento, CA 95691 Phone # 916-373-1166 <br />Contact Dulcinea Covan Fax # 916-373-1173 <br />Test Technician Ran Powell <br />5. TEST RESULTS <br />Measuring tquipment usea: L;alawell System zuui / wanon tngineering (Level unange Inai <br />Description Tank #1 Tank #2 Tank #3 <br />Product contained <br />Gasoline - 87 Gasoline - 89 Gasoline - 91 <br />Spill container capacity (US gallons) <br />5 <br />Spill container manufacturer <br />OPW <br />Spill container depth (inches) <br />12.00 <br />Is the spill container located in a sump? <br />Yes <br />Does sump have a liquid sensor installed? <br />No <br />Condition of spill container prior to testing <br />Dry <br />Portion of spill container tested <br />Entire <br />Depth of water level from bottom (inches) <br />10.50 <br />Wait time for water level to stabilize (hr:min) <br />0:02 <br />Test start time <br />1:55 PM <br />Test end time <br />2:25 PM <br />Test duration (hr:min) <br />0:30 <br />Change in water level (t 0.000 inches) <br />0.000 <br />Pass/Fail threshold (0.005 inches / % Hr.) <br />0.005 <br />TEST RESULT <br />PASS <br />S. COMMENTS <br />This is a retest after the 87 spill container was replaced. <br />Technician Signature % �`"�'� Date July 22, 2011 <br />