The following is an itemized list of underground storage tank violations that have not <br /> been addressed for GRUPE COMMERCIAL COMPANY HANGER #2 as of April 26, <br /> 2018. <br /> Open violations from December 15,2017 inspection <br /> Violation#302 -UST system incapable of detecting leak from primary into secondary containment(pre-Jul <br /> 2003). <br /> The annular sensor failed to activate an audible and visual alarm when tested and, therefore, the tank is not <br /> monitored. The interstitial space shall be monitored with a monitoring system connected to an audible and visual <br /> alarm system. Immediately contact a properly licensed, trained, and certified contractor to replace the failed <br /> component with a functional component(LG 113-x listed, if applicable) under permit and inspection of the EHD <br /> within one business day. <br /> Page 1 of 1 <br />