Laserfiche WebLink
State Water Resources Control Board Page 2 of 4 <br /> Detection time sec . <1 <1 <br /> Fall time manual reset manual manual reset <br /> reset <br /> Precision -standard 0.003474 0.001923 0.005329 <br /> deviation in <br /> Lower detection limit in 0.357 0.321 0.369 <br /> Model EOS100 Discriminating Sensor(5 sensing levels) <br /> Detection time(sec) <1 <1 <1 <br /> Fall time manual reset manual automatic reset when <br /> reset water level drops <br /> Precision in <br /> Level 1 (low level switch) 0.005 0.002 0.003 <br /> Level 2 0.006 0.002 not evaluated <br /> Level 3 0.004 0.002 not evaluated <br /> Level 4 0.004 0.002 not evaluated <br /> Level 5 (high level 0.004 0.002 0.004 <br /> switch) <br /> Lower detection limit(in) <br /> Level 1 (low level switch) 0.536 0.551 0.550 <br /> Level 2 1.266 1.226 not evaluated <br /> Level 3 2.097 2.074 not evaluated <br /> Level 4 2.858 1 2.895 L not evaluated <br /> Level 5(high level 3.569 3.57 3.596 <br /> switch) <br /> Model 510 Discriminating Se sor <br /> Detection time 5-10 min 1-2 hr <1 sec <br /> Fall time(sec) Replaceable Replaceable <1 <br /> Precision -standard <0.0001 <0.0001 0.0045 <br /> deviation in <br /> Lower detection limit in 0.058 1 0.058 1 11.566 1 <br /> Model 516 Discriminating Se sor <br /> Detection time(sec) <1 <1 <1 <br /> Fall time <1 <1 <1 <br /> Precision -standard 0.0038 0.0032 0.0020 <br /> deviation in <br /> Lower detection limit in 0.340 0.369 0.389 <br /> Model DFR-1 Liquid Level <br /> Switch <br /> Detection time (sec) <1 <br /> http://www.waterboards.ca.gov/water-issues/programs/ust/leak_prevention/lgl 13/vendors/b... 6/4/2009 <br />