Laserfiche WebLink
P <br /> SWRCB January 2002 Page 3 of 7 <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: ❑Piping Manufacturer VIndustry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used:4"Liquid-Filled Gauge Equipment Resolution:+/-.002 <br /> Piping Run#87 A Piping Run#87 B Piping Run#89 A Piping Run#89 B <br /> Piping Material: Fiberglass Fiberglass Fiberglass Fiberglass <br /> Piping Manufacturer: Ameron Ameron Ameron Ameron <br /> Piping Diameter: 3" 3" 3" 3" <br /> Length of Piping Run: 100' 100' 100' 100, <br /> Product Stored: Gasoline Gasoline Gasoline Gasoline <br /> Method and location of Reducer Boots/Fitt Reducer Boots/Fitt Reducer Boots/Fit Reducer Boots/Fitt <br /> piping-run isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 10 Min 10 Min 10 Min 10 M i n <br /> starting test: <br /> Test Start Time: 9:00am 10:15am 11:30am 12:45pm <br /> Initial Reading(RI): 5.Opsi 5.Opsi 5.Opsi 5.Opsi <br /> Test End Time: 10:OOam 11:15am 12:30pm 1:45pm <br /> Final Reading(RF): 5.Opsi 5.Opsi 5.Opsi 5.Opsi <br /> Test Duration: 1 Hour 1 Hour 1 Hour 1 Hour <br /> Change in Reading(RF-RI): None None None None <br /> Pass/Fail Threshold or No detectable loss No detectable loss No detectable los: No detectable loss <br /> Criteria: <br /> Test Result: Pass ❑Fail Pass I p Fail ss,:; ❑Fail Pass ❑Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />