SWRCB,January 2002 Page 3 of 7 <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: ❑Piping Manufacturer VIndustry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used:4"liquid-filled gauge Equipment Resolution:+/-.01 <br /> MEMNON Pipin�Run Diesel Piping Run# Piping Run# Piping Run# <br /> Piping Material: Fiberglass <br /> Piping Manufacturer: Ameron <br /> Piping Diameter: 3" <br /> Length of Piping Run: 100' <br /> Product Stored: Diesel <br /> Method and location of Reducer Boots/Fitt <br /> piping-run isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 30 M i n <br /> starting test: <br /> Test Start Time: 1:30prn <br /> Initial Reading(Rj): 5.0 psi <br /> Test End Time: 2:30prn <br /> Final Reading(RF): 5.0 psi <br /> Test Duration: 1 Hour <br /> Change in Reading(RF-RI): None <br /> Pass/Fail Threshold or +/-.01 <br /> Criteria: <br /> Test Result: Pass ❑Fail ❑ 'Pass 0 Fail Q Pass ! ❑Fail ❑ Pass ❑Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Replaced test boots in STP and udc's on diesel secondary <br />