SWRCB. January 2002 <br />4. TANK ANNULAR TESTING <br />Page 2 of 7 <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for tailed tests) <br />REPAIRED RISER (REPLACED RISER) RETESTED 10 HG AFTER BACKFILLING RISER <br />AND BACKFILLING RISER PIPE BOTH TESTS DONE AT 10 HG VACUUM, NO DROP ON <br />EITHER TEST. <br />1 Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment, such as systems <br />that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment testing. {California Code of Regulations, Title 23, <br />Section 2637(a)(6)] <br />Tank # 1 <br />Tank # <br />Tank # <br />Is Tank Exempt From <br />Testing? 1 <br />[ ] Yes [X] No <br />[ ] Yes [ ] No <br />[ ] Yes [ ] No <br />Tank Capacity: <br />10,000 -GALLON <br />Tank Material: <br />FIBERGLASS <br />Tank Manufacturer: <br />XERXES <br />Product Stored: <br />UNLEAD GAS <br />Wait time between <br />applying <br />pressure/vacuum/water <br />and starting test: <br />10 MINUTES <br />Test Start Time: <br />11:50 A.M. 1. 16.03 <br />Initial Reading (Rl): <br />10 HG <br />Test End Time: <br />1:00 P.M. 1. 16.03 <br />Final Reading (Rf): <br />10 HG <br />Test Duration: <br />1 HOUR, 10 -MINUTES <br />Change in Reading (Rf- <br />R1 <br />-0- <br />Pass/Fail Threshold or <br />Criteria: <br />Less than 2 HG drop in one <br />hour <br />Test Result: <br />IX] PASS 1, ] 'FAIL <br />I ] PASS I ]TAIL <br />[ ] PASS [ ] FAIL <br />Was sensor removed for <br />testing? <br />[X] YES [ ] NO <br />[ ] N/A <br />[ ]YES [ ] NO <br />[ ] N/A <br />[ ] YES[ ] NO <br />[ ]N/A <br />Was sensor properly <br />replaced & verified <br />functional after testing? <br />[X]YES [ ] NO <br />[ ] N/A <br />[I YES [ ] NO <br />[ ] N/A <br />[ ] YES [ ] NO <br />[ ] N/A <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for tailed tests) <br />REPAIRED RISER (REPLACED RISER) RETESTED 10 HG AFTER BACKFILLING RISER <br />AND BACKFILLING RISER PIPE BOTH TESTS DONE AT 10 HG VACUUM, NO DROP ON <br />EITHER TEST. <br />1 Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment, such as systems <br />that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment testing. {California Code of Regulations, Title 23, <br />Section 2637(a)(6)] <br />