The following table (attached) summarizes the results of the AcuRite® volumetric line testing. <br />4.0 CERTIFICATIOK <br />Shirley Environmental Testing, L.L.C. certifies that the UST systems listed in the above tables <br />have been tested utilizing leak detection methods which meet the prescribed leak rate testing <br />standard of 0.10 gph with a minimum probability of detection of 95% and a 5% probability of a <br />false alarm. Shirley Environmental Testing, L.L.C. further certifies that the protocol for each test <br />method was strictly adhered to, and all precision tightness testing performed by Shirley <br />Environmental Testing, L.L.C. was conducted in accordance with EPA 40 CFR parts 280.430 <br />and 280.44(b) and the National Fire Protection Association, Bulletin NFPA 329 criteria. <br />The discussion in this report represents our professional opinions. Our conclusions and opinions <br />are derived from information available at this time. We do not guarantee that undiscovered <br />conditions will not become evident in the future. <br />Thank you for the opportunity to work on this project with you. Should you have any questions <br />regarding this report or any aspect of this project, please do not hesitate to contact me at (800) <br />447-3490. <br />Sincerely, <br />Mark T. Shirley <br />Shirley Environmental Testing, L.L.C. <br />Attachments <br />OA <br />