Laserfiche WebLink
SWRCB,January 2002 0 0 Page_ja of <br /> 21. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: 0 UDC Manufacturer 0 Industry Standard X Professional Engineer <br /> 0 Other(Specify) <br /> Test Method Used: 0 Pressure 0 Vacuum X Hydrostatic <br /> 0 Other(Specify) <br /> Test Equipment Used: MTS Mag Probe W/TDU Meter Equipment Resolution: .001" <br /> UDC#21-Sattefite UDC#22 UDC#22-Satellite UDC#23 <br /> UDC Manufacturer: Owens Co in Owens Corrin Owens Co2!!p <br /> Owens CorrinS <br /> UDC Material: E!tLr&1ass Fiberglass Fiberglass Fiberglass <br /> UDC Depth: 26" 26" 26" 267' <br /> Height from UDC Bottom to Top 9" 911 91 9" <br /> of Hi est Pi ing Penetration.. <br /> Height from UDC Bottom to 5" 5'7 5" 577 <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Good Good Good Good <br /> Portion of UDC Tested12" 1219 1211 12" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both 0 Yes XNoDNA 0 Yes XNo DNA DYes, X No 0 NA El Yes X No [INA <br /> product and water)?* <br /> Turbine shutdown T§vnse time N/A N/A N/A N/A <br /> Is system programmed for fail- 0 Yes X No 0 NA 0 Yes XNo DNA DYes X No 0 NA 0 Yes X DNA <br /> safe shutdown?* <br /> Was fail-safe verified to be 0 Yes X No 0 NA 0 Yes X No DNA D Yes X No El NA 0 Yes XNo DNA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 10 in 10 in 10 in 10 in <br /> st�m test <br /> Test Start Time: 13:00 13:00 13:40 13:40 <br /> Initial Reading(R,): Ww" 0,0001, 0.00w; 0.0001, <br /> Test End Time: 13:12 13:12 13:52 13:52 <br /> Final Reading(RF): 0.0001, 0.000, 0.000" 0.002" <br /> Test Duration: 12 in 12 in 12 in 12 in <br /> Change in ReadinS(RF-Ri)-. 0.000" OXM" <br /> Pas ail Threshold or Criteria: +/-.002" +/-.002" +/-.002" <br /> X Pun D Fa FOR Pos 1 0 Fag <br /> X P%ss �Cl <br /> Was sensor removed for testing? X Yes 0 No 0 NA X Yes 0 No 0 NA X Yes 0 No 0 NA X Yes 0 No 0 NA <br /> testing? <br /> Was sensor properly replaced <br /> n j <br /> ? X Yes 0 No 0 NA XYes ONo DNA XYes DNo DNA X Yes 0 No 0 NA <br /> verified functional after testin ? I I <br /> Co (include in orrrzatiort o r airs triads riot to testi , and recommended folloK,-upforfailed tests) <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to my of the questions indicated with an <br /> asterisk(*)is"NO"or"NK',the entire UDC must be tested. (See SWC B LG-160) <br />