Laserfiche WebLink
SWRCB,January 2002 Page 19 <br /> 7. UNDER-DISPENSER CONTAINMENT (UDC)TESTING <br /> Test Method Developed By: F-1 UDC Manufacturer ❑ Industry Standard X� Professional Engineer <br /> El Other (Sped) <br /> Test Method Used: F] Pressure Vacuum Hydrostatic <br /> El Other (Specify) <br /> Test Equipment Used: vp1t Equipment Resolution: vplt to gph <br /> UDC# 21sat UDC# 22 UDC# 22sat UDC# 23 <br /> UDC Manufacturer: unknown unknown unknown unknown <br /> UDC Material: fiberglass fiberglass fiberglass fiberglass <br /> UDC Depth: 28" 28" 28" 28" <br /> Height from UDC Top to Top of 10" 1011 10" 101' <br /> Highest Piping Pentration: <br /> Height from UDCTop to Lowest <br /> Electrical Pentration: <br /> Condition of UDC prior to testing: good good good good <br /> Portion of UDC Tested: 1 1211 1211 1211 1211 <br /> Does turbine shut down when <br /> sump sensor detects liquid(both �Yes❑No[:]N E]Yes[:]N00N Yes❑No�N a Yes❑No�1 <br /> product and water)?* <br /> Turbine shutdown response time: 2-5 SEC 2-5 S EC 2-5 S EC 2-5 SEC <br /> Is system programmed for fail-safe ❑ � ❑ ❑ � ❑ ❑ _]NA❑ ❑ <br /> shutdown?* Yes N N X Yes N N X Yes N X Yes No <br /> X <br /> Was fail-safe verified to be ❑ � � ❑ � ❑ � ❑ ❑ <br /> operational?* X Yes N N X❑Yes N N X Yes N N X Yes No <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5MIN 5MIN 5MIN 5MIN <br /> test: <br /> Test Start Time: 15:19 15:43 15;08 15:06 <br /> Initial Reading(Rl): 4.907 9.124 3.481 1.439 <br /> Test End Time: 15:34 15:58 15:23 15:21 <br /> Final Reading(RF): 4.922 9.128 3 .488 1.439 <br /> Test Duration: 15min 15min 15min 15min <br /> Change in Reading(RF-Ri ): .OOIGPH OOOGPH OOOGPH OOOGPH <br /> Pass/Fail Threshold or Criteria: .05GPH .05GPH .05GPH .05GPH <br /> Was sensor removed for testing? LfjX Yes N NA X Yes R N NA Yes N NA X Yes No <br /> Was sensor properly replaced and � � ❑ � � � ❑ ❑ ` N <br /> verified functional after testing? X Ye N NA X Ye N NA X Ye N NA X Yes N� <br /> Comments- (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> DISP. 19 on the backside was not tested due to a tear in the boot. <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested.If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />