JONES COVEY CROUP, INC. <br />PEVE LOPE RS/CONSTRUCTORS <br />MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br />SITE: Pilot -Flying #618 <br />State Facility # <br />DATE: 5/24/2011 <br />CONTACT: Manager <br />PHONE: 209-599-4141 <br />!OB #: 9647 <br />Sump Pump # <br />TK#1 <br />TK#2 <br />TK#3 <br />TK#4 <br />Truck <br />Product <br />Diesel <br />Truck DSL <br />Truck DSL <br />87 unleaded <br />LD Manufacturer <br />Red jacket <br />Vaporless <br />Vaporless <br />Vaporless <br />LD Model <br />116-058 <br />99LD2000 <br />99LD2000 <br />99LD2000 <br />Sump Condition <br />Good <br />Good <br />Good <br />Good <br />Operation Pressure <br />37 psi <br />34 psi <br />39 psi <br />27 psi <br />(PSI) <br />Opening Time (Sec) <br />7 sec <br />3 sec <br />8 sec <br />17 sec <br />Metering Pressure <br />10 psi <br />11 psi <br />10 psi <br />11 psi <br />(PSI) <br />Functional Element <br />10 psi <br />21 psi <br />20 psi <br />15 psi <br />Holding Pressure <br />Leak Rate LD <br />3 GPH <br />3 GPH <br />3 GPH <br />3 GPH <br />Detected (GPH) <br />Does LD Detect 3 GPH <br />Yes <br />Yes <br />Yes <br />Yes <br />Leak Rate? <br />LD Serial <br />5103- N/A <br />07031408 <br />07031407 <br />03040274 <br />Comments: <br />All leak detector passed. <br />Technician: Frank Vasquez <br />9595 Lucas Ranch Rd. # 100 Rancho Cucamonga, CA 91730 <br />Office (909)972-7581 Fax (909) 484-0300 Fax California State License # 804431 A,B,HAZ <br />