Laserfiche WebLink
n <br />SWRCB, January 2002 Page 14 of 14 <br />7. UNDER -DISPENSER CONTAINMENT UDC TESTING <br />Test Method Developed By: ❑ UDC Manufacturer A Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum 9 Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: INCON TS -STS <br />Equipment Resolution: +/-0.002" <br />UDC # 29 Master <br />UDC Manufacturer: Unknown <br />UDC # 29 Satellite <br />Unknown <br />UDC # 30 Master <br />Unknown <br />UDC # 30 Satellite <br />Unknown <br />UDC Material. Fiber lass <br />Fiberglass <br />Fiberlass <br />Fiberglass <br />UDC Depth: 30" <br />30" <br />30" <br />30" <br />Height from UDC Bottom to Top 14" <br />of Highest Piping Penetration: <br />13" <br />14" <br />13" <br />Height from UDC Bottom to 91, <br />Lowest Electrical Penetration: <br />91, <br />10" <br />9" <br />Condition of UDC prior to <br />Dry <br />testing: <br />Dry <br />Dry <br />Dry <br />Portion of UDC Tested' 18" <br />17" <br />18" <br />17" <br />Does turbine shut down when <br />UDC sensor detects liquid (both ❑ Yes []No X NA <br />product and water)?' <br />❑ Yes ❑ No X NA <br />❑ Yes ❑ No J NA <br />❑ Yes ❑ No A NA <br />Turbine shutdown response time <br />Is system programmed for fail- ❑ Yes ❑No ® NA <br />safe shutdown?` <br />F-1Yes Ll No !X NA <br />F1 Yes 11 No X NA <br />-7 Yes El No 9 NA <br />Was fail-safe verified to be ❑ Yes ❑ No JNA <br />operational?* <br />❑ Yes ❑ No X NA <br />❑ Yes ❑ No J NA <br />❑ Yes ❑ No 9 NA <br />Wait time between applying <br />pressure/vacuum/water and 15min <br />starting test <br />15min <br />15min <br />15min <br />Test Start Time: 2:55pm <br />1:57pm <br />4:46pm <br />1:13 m <br />Initial Reading (R,): 3.9981" <br />3.1207" <br />3.1810" <br />5.1270" <br />Test End Time: 3:10pm <br />2:12 m <br />5:02 m <br />1:28pm <br />Final Reading (RF): 3.9976" <br />3.1220" <br />3.1800" <br />5.1261" <br />Test Duration: 15min <br />15min <br />15min <br />15min <br />Change in Reading RF -RI): 0.0005" <br />0.0013" <br />0.0010" <br />0.0009" <br />Pass/Fail Threshold or Criteria: +/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />Test Result: 19 Pass Q Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />Was sensor removed for testing? ® Yes ❑No ❑ NA <br />® Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ❑ NA <br />Was sensor properly replaced and id <br />verified functional after testin ? Yes ❑No 11 NA <br />Yes 11 No 11 NA <br />Yes 71 No El NA <br />®Yes [I No El NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />r r <br />8 201'1 <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />