Laserfiche WebLink
SECONDARY LINE TESTING <br />Test Method By: 0 Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: • Pressure o vacuum o Hydrostatic o Other (see below) <br />Measuring Equipment Used: Pressure Gauge (range 0 to 15 psig) <br />Descrintion Line #5 Line#6 <br />Tank product <br />Gasoline - 91 - E <br />Gasoline - 91 - W <br />Pipe manufacturer <br />Environ <br />Environ <br />Pipe material <br />Poly <br />Poly <br />Primary pipe diameter (inches) <br />1.5 <br />1.5 <br />Secondary pipe diameter (inches) <br />2 <br />2 <br />Method of secondary pipe isolation <br />Co -ax Fitting <br />Co -ax Fitting <br />Location of secondary pipe isolation <br />Sump <br />Sump <br />Estimated length of piping run (feet) <br />100 <br />110 <br />(include length of branch runs) <br />PASS <br />FAIL <br />Wait time for pressure to stabilize (hr:min) <br />0:10 <br />0:10 <br />Test start time <br />12:30 PM <br />1:20 PM <br />Initial pressure (psig) <br />5.0 <br />5.0 <br />Test end time <br />1:30 PM <br />1:25 PM <br />Final pressure (psig) <br />5.0 <br />4.0 <br />Test duration (hr:min) <br />1:00 <br />0:05 <br />Change in pressure (psig) <br />0.0 <br />1.0 <br />Pass/Fail threshold (psig) <br />0.5 <br />0.5 <br />TEST RESULT <br />PASS <br />FAIL <br />Comments: <br />© 2006 Walton Engineering, Inc. <br />