Laserfiche WebLink
1111100 Field Test Apparatus Page 1 of 1 <br /> .gTanknoiogy Line Leak Detector Test <br /> Work Order: 2303173 Date: 3/23/2012 <br /> Site Name/ ID: 7-ELEVEN #32262, MKT 2368 (N-3940-1 / 32262 <br /> Address: 2360 W GRANTLINE I-205 OFF RAMP <br /> City: TRACY State: CA Zip: 95376 <br /> Tank ID 4 5 6 <br /> Product REG UNLEAD MIDGRADE PREMIUM <br /> Product Line 1 1 1 <br /> Tested From <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-200C FE Petro MLD Vaporless LD-200 <br /> Serial No. unreadable unreadable 07071145 <br /> Pump Operating Pressure(psi) 34.00 30.00 30.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 34.00 30.00 30.00 <br /> 'N/A for Electronic LD's <br /> Resiliency(ml) 235.00 315.00 240.00 <br /> 'N/A for Electronic Lo's <br /> Metering PSI 18 10 17 <br /> `NIA for Electronic LD's <br /> Opening Time(sec) 7 9 9 <br /> *N/A for Electronic LD's <br /> Test Results Pass Pass I Pass <br /> Technician Comments: <br /> Technician Name: Steven Willl1lems Certification#: 1931 <br /> Technician Signature: v.J <br /> Environmental Compliance for Petroleum Systems <br /> ®2010 Tanknology Inc.,Austin,Tx. All rights reserved. tanknology.com <br />