Laserfiche WebLink
Page 4 of 8 <br /> 3. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ®Industry Standard Q Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> Sump#87 Sump# 91 <br /> Sump Diameter: 48" 48" <br /> Sump Depth: 79" 79" <br /> Sump Material&Manufacturer: Fiberglass Fiberglass <br /> Height from Tank Top to Top of 1259 1299 <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 2799 2719 <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Fair Fair <br /> Portion Of Sum Tested' Above highest Above highest Above highest Above highest <br /> Sump enetration penetration penetration penetration <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes❑No®NA ❑Yes❑No®NA ❑Yes❑No®NA ❑Yes❑No®NA <br /> product and water)?` <br /> Turbine shutdown response time <br /> Is system programmed for fail-safe <br /> shutdown?* E]Yes E]No®NA ❑Yes F1No®NA ❑Yes❑No®NA ❑Yes F1No®NA <br /> Was fail-safe verified to be ®Yes❑No®NA ❑Yes❑No®NA ❑Yes❑No E NA Q Yes®No®NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 30 minutes 30 minutes 30 minutes 30 minutes <br /> test: <br /> Test Start Time: 12:05pm 12:09pm <br /> Initial Reading(RI): 0.5952 2.3099 <br /> Test End Time: 12:20pm 12:24pm <br /> Final Reading(RF): 0.5948 2.3103 <br /> Test Duration: 15 min 15 min <br /> Change in Reading(RF-Ri): 0.00034 0.00045 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> r ter a rya '"'' . <br /> Was sensor removed for testing? ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and E Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> i If the entire depth of the sump is not tested,specify how much was tested. If the answer to ggy of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />