Laserfiche WebLink
SWRCB,January 2002 ,n n 2E ;'Page of <br /> , <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes❑ � <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested❑ <br /> Test Method Developed By: ❑Spill Bucket Manufacturer ❑✓ Industry Standard El Professional Engineer <br /> El Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> 0 Other(Spec) inches-1 hr visual test <br /> Test Equipment Used: See attached testing procedures Equipment Resolution: <br /> Spill Box#87 FB Spill Box#91 FB Spill Box#87 VB Spill Box#91 VB <br /> Bucket Diameter: 12" 12" 12" 12" <br /> Bucket Depth: 12.5" 12.5" 14" 14" <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes 15 minutes 15 minutes <br /> starting test: <br /> Test Start Time: 8:39am 8:46am 8:39am 8:46am <br /> Initial Reading(Ri): 11.5 ie=hes-,hr isual test 11.75 Inches-,In,muM is. 13.25 .ch..-,In,v—ltest 13.375 trmhs-,h,AWAn <br /> Test End Time: 9:39am 9:46am 9:39am 9:46 <br /> Final Reading(RF): 11.5 nch..-,In,0-1 test 11.75 inches-I In,"s�1- 13.25 inch.,-,h,vi-11- 13.375 Inc,..-,h,vis"V <br /> Test Duration: 1 hr 1 hr 1 hr 1 hr <br /> Change in Reading(RF-Ri): 0 0 0 0 <br /> Pass/Fail Threshold or 0 0 0 0 <br /> Criteria: <br /> Test Result: ElPass ❑Fair` ❑✓ Pass ❑Fail Q Pass ❑Fail ✓❑Pass ❑Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 87 & 91 fill buckets - replaced lower o'rings <br />