Laserfiche WebLink
s <br /> P <br /> KEGEIVED <br /> LDT 5000 Field Test Apparatus ENVIRONMENTAL <br /> f 2 <br /> anknlogy <br /> J/ Line Leak Detector Test <br /> H up A .. E <br /> Work Order: 2326364 Date: 2/10/2016 <br /> Site Name/ID: CHEVRON#208117/208117 <br /> Address: 755 S.TRACY BLVD <br /> City: TRACY State: CA Zip: 95376 <br /> Tank ID T1 T2 T2 T2 T2 T1 <br /> Product PREMIUM REGULAR REGULAR REGULAR REGULAR PREMIUM <br /> Product Line 1 1 1 1 1 1 <br /> Tested From 10 11 11 11 11 11 <br /> Existing/New Existing Existing Existing Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD Veeder Root PLL <br /> Serial No. 015583 235887 235887 235887 235887 015583 <br /> Pump Operating Pressure(psi 38.00 38.00 38.00 38.00 38.00 38.00 <br /> Calibrated Leak(mi/min) 189.0 189.0 189.0 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 3.00 3.00 3.00 <br /> Holding PSI <br /> N/A for Electronic Lo's <br /> Resiliency(ml) <br /> N/A for Electronic Lo's <br /> Metering PSI <br /> N/A for Electronic Lo's <br /> Opening Time(sec) <br /> N/A for Electronic Lo's <br /> Test Results Fail Fail Fail Fail Pass Fail <br /> Technician Comments:CHANGED BOTH SIPHON JETS AND PURGED OVER 300 GALLONS OF GAS FROM BOTH GRADES <br /> Technician Name: Gilbert Garcia Certification#: 100037 <br /> Technician Signature: - Expire Date: 8/5/2016 <br /> Environmental Compliance for Petroleum Systems <br /> ©2016 Tanknology Inc.,Austin,TX All rights reserved. tanknology.com <br />