w <br /> `6 AEGEIVED <br /> 1111100 Field Test Apparatus MAR 0 6 2015 <br /> Tanknoiogy Line Leak Detector Test Page 1 of 1 <br /> [ _, <br /> Work Order: 2321578 Date: 2/23/2015 <br /> Site Name/ID: CHEVRON#208117/208117 <br /> Address: 755 S.TRACY BLVD <br /> City: TRACY State: CA Zip: 95376 <br /> Tank ID T 1 T 2 <br /> Product PREMIUM REGULAR <br /> Product Line 1 1 <br /> Tested From 9 9 <br /> Existing/New Existing Existing <br /> echanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLL <br /> Serial No. 015583 235887 <br /> ump Operating Pressure(psi) 30.00 30.00 <br /> alibrated Leak(ml/min) 189.0 189.0 <br /> alibrated Leak(gph) 3.00 3.00 <br /> Holding PSI <br /> N/A for Electronic LD's <br /> Resiliency(ml) <br /> N/A for Electronic LD's <br /> Metering PSI <br /> N/A for Electronic LD's <br /> pening Time(sec) <br /> N/A for Electronic LD's <br /> est Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jarrod Cooke Certification#: 1352 <br /> Technician Signature: Expire Data: 2/10/2015 <br /> Environmental Compliance for Petroleum Systems <br /> 02015 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.corn <br />