Laserfiche WebLink
S A NA A Q U I N Environmental Health Department <br /> COUNTY <br /> Undergruntl Storage Tank, Program inspection Report f <br /> Facility Name: Facility Address: Date: <br /> PACIFIC CAR WASH/MARKETPLACE INC 4405 PACIFIC AVE, STOCKTON May 15, 2018 <br /> US System Observations <br /> 319 CCR 2635(b) No spill bucket,failed to contain five gallons,or failed to provide a means to keep it empty ❑V ❑R ❑COS <br /> 320 CCR 2635(b)(2) Overfill prevention system not present or failed to meet overfill requirements ❑V ❑R ❑COS <br /> 321 CCR 2635(b)(2) Overfill prevention was overridden ❑V ❑R ❑COS <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status ❑V ❑R ❑COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status ❑V ❑R ❑COS <br /> 324 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V ❑R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored ❑V ❑R ❑COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 329 HSC 25298 Failed to comply with all permanent closure requirements ❑V ❑R ❑COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system ❑V ❑R ❑COS <br /> 331 CCR 2630(d) Secondarily contained piping not maintained to allow liquid to drain into sump ❑V ❑R ❑COS <br /> 332 CCR 2631(b),2631(d) Primary and/or secondary containment not constructed in accordance with the established standards ❑V ❑R ❑COS <br /> SingCrllValfed Non-Pssurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 77 <br /> Other Violations~ <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS 1,CLASS 11,or iiiNOR-NoSce W Comply) <br /> Item# Remarks <br /> 307 CCR 2631(g), 2632(c) Monitoring system of the interstitial space of a double walled system not maintained. <br /> The 87/91 split Veeder Root 420 annular sensor failed to activate an audible and visual alarm when tested and, <br /> therefore,the tank is not monitored. According to the technician,there was no signal to the sensor.The interstitial <br /> space shall be monitored with a monitoring system connected to an audible and visual alarm system. The sensor <br /> was replaced and retested during the inspection. A"UST Retrofit Verification with Inspector Already Onsite"form <br /> has been completed and provided to the operator and contractor. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> FA0007787 PR0508452 SCO01 05/15/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 3 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />