Laserfiche WebLink
SWRCB,January 2002 Page 15 <br /> 7. UNDER-DISPENSER CONTAINMENT (UDC) TESTING <br /> Test Method Developed By: F-1 UDC Manufacturer Industry Standard ❑X Professional Engineer <br /> El Other (Specify) <br /> Test Method Used: FI Pressure ❑ Vacuum Hydrostatic <br /> El Other (Specify) <br /> Test Equipment Used: vpl t Equipment Resolution: vplt to gph <br /> UDC# 22 UDC# 22sat UDC# 23 UDC# 23sat <br /> W.f. w.f. W.f. W.f.UM <br /> 77 fiberglass fiberglass fiberglass fiberglass <br /> UDC Depth: 3111 3111 3111 31TI <br /> Height from UDC Top to Top of 9" 9„ 911 9 IT <br /> Highest Piping Pentration: <br /> Height from UDCTop to Lowest 1/211 1/2" 1/211 1/2" <br /> Electrical Pentration: <br /> Condition of UDC prior to testing: good good good good <br /> Portion of UDC Tested: 1 1111 1111 1111 111t <br /> Does turbine shut down when <br /> sump sensor detects liquid(both X❑yes❑N�N � <br /> Yes No❑N Yes❑N�N I Yes <br /> []Not <br /> product and water)?* <br /> Turbine shutdown response time: 2-5sec 2-5sec 2-5sec 2-5 s e c <br /> Is system programmed for fail-safe ❑ ❑ `� ❑ ❑ � ❑ ❑ `� ❑ ❑ <br /> shutdown?* X Yes N N X Yes N N X Yes N N X Yes No <br /> Was fail-safe verified to be � ❑ � � ❑ �V <br /> operational?* X❑Yes N N X❑Yes N N X❑Yes N N X❑Yes No <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5MIN 5MIN 5MIN 5MIN <br /> test: <br /> Test Start Time: 1:30 2 :47 2 :20 2 :49 <br /> Initial Reading(Rl): 6.670 5.836 6.902 2.193 <br /> Test End Time: 1:45 3 :02 2 :35 3 :05 <br /> Final Reading(RF): 6.670 5.836 6.902 2.193 <br /> Test Duration: 15min 15min 15min 15min <br /> Change inReading(RF-Rl ): .000gph .000gph .000gph .000gph <br /> Pass/Fail Threshold or Criteria: .05gph .05gph .05gph .05gph <br /> _. <br /> Was sensor removed for testing? X YesE]N NA EYes❑No❑NA�Yes❑No❑NA Yes No <br /> Was sensor properly replaced and ❑ � � ❑ s0 � o ❑ <br /> verified functional after testing? X Ye N NA X Ye N NA X Ye N NA X yes N <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested.If the answer to aof the questions indicated with an <br /> asterisk(*)is "NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />