Laserfiche WebLink
TLS -350 Monitoring System Requirements <br />• TLS -350 with ECPU2 <br />• NVMEM 203 <br />• RS -232 Interface Module for On-site PC report access <br />• Smart Sensor Module <br />• Dispenser Interface Module (DIM) <br />• ISD Software Enhancement Module (SEM) <br />• Site Shutdown Control Hardware <br />Alarm Table <br />The following table contains a list of warnings and alarms posted or <br />used by the ISD system: <br />Balance <br />ISD <br />Assist <br />ISD <br />Warning <br />Days to <br />Alarm <br />Description <br />X <br />X <br />ISD DEGRD PRESSURE <br />30 ' ` <br />75" percentile of 30 days' ullage <br />332250-1 <br />Seven Input Smart Sensor Modules <br />1 per seven or eight <br />Smart Sensors <br />3 6-004 Eight Input Smart Sensor Module <br />pressure that exceeds 0.3 IWC <br />X <br />X <br />ISD GROSS PRESSURE <br />7 <br />951' percentile of 7 days' ullage <br />when mounted on <br />_ <br />Vent Stack <br />pressure that exceeds 1.3 IWC <br />X <br />X <br />ISD VAPOR LEAKAGE <br />7 <br />Containment system leaks at two <br />times the TP 201.3 standard <br />X <br />X <br />ISD SENSOR OUT <br />7 <br />Failure of Sensor Self -test <br />X <br />X <br />ISO SETUP <br />7 <br />Failure of Setup Test <br />X <br />Hnn: DEGRD COLLECT <br />7 <br />7 -day Degradation AA - Test <br />X <br />Hnn: GROSS COLLECT <br />1 <br />1 -day Gross AIL Test Warning <br />X <br />Hnn: FLOW COLLECT <br />1 <br />Vapor collection flow perfomance <br />is less than 50% <br />X <br />ISD VP PRESSURE <br />1 <br />9011 percentile of 1 -day ullage <br />pressure exceeds 2.5 IWC <br />X <br />ISD VP EMISSIONS <br />1 <br />Mass emission exceeded the <br />certified threshold <br />X <br />ISD VP Status <br />Failure of Vapor Processor Effluent <br />Emissions or Duty Cycle Test <br />Assist ISD <br />Numer <br />Description <br />Requirement <br />330020-4 <br />Assist Vapor Flow M ,, it <br />1 per dispenser <br />330020-515 <br />861190-201 <br />I aporPr ure Sensor Kit' <br />NEW Wirel apo ure Sensor Kit' <br />1 per site <br />330020-715 NEW por Pressure Sensor Site <br />332250-1 <br />Seven Input Smart Sensor Modules <br />1 per seven or eight <br />Smart Sensors <br />3 6-004 Eight Input Smart Sensor Module <br />Balance ISD <br />Part Numer <br />Description <br />Requirement <br />330020-585 <br />Balance Vapor Flow Meter Kit <br />1 per dispenser <br />330020-515 <br />Wired Vapor Pressure Sensor Kit' <br />1 per site <br />861190-201 NEW Wireless Vapor Pressure Sensor Kit' <br />330020.715 NEW Vapor Pressure SensorSite Start-up Kit'' <br />332250-001 <br />Seven Input Smart Sensor Modules <br />1 per seven or eight <br />Smart Sensors <br />329356-004 Eight Input Smart Sensor Module <br />847490-315 <br />PMC Port Controller Module <br />1 per TLS Console <br />TLS -350 Software/Memory <br />Upgrade Options for ISD <br />Part Numer Description Requirement <br />331500-358 ECPU2, latestV.3XX software, NVMEM 203 <br />331500-322 Latest V.3XX software, NVMEM 203 <br />332966-203 NVMEM 203 (report storage) 1 per Console <br />330160-004 ISD Software Enhancement Module ISEM)' <br />331500-353 TLS V. XX software <br />Optional ISD Components <br />Part Numer <br />Description <br />Requirement <br />331408-0 <br />Dispenser Control Module fo gle <br />1 module per <br />Dispenser Shut <br />4 dispensers <br />330020-630 <br />Vapor Press nsor Kit for Mounting <br />1 per Console <br />Ve ack' <br />i 2. Can only be used on wireless installations. <br />zUniversal <br />1 per Pressure Sensor <br />330020-716 <br />Enclosure Box <br />when mounted on <br />_ <br />Vent Stack <br />330 20-717 <br />NEW Vapor Pressure Sensor Drying Tube Kit <br />Repla, M -N Part <br />_ e e <br />ISD Pressure Sensor <br />(Installation Option 1) <br />Wired only To learn more, contact us at 888.561.7942, or visit wwwveeder.com. <br />ilf I® ®C 125 Powder Forest Drive, PO. Box 2003, Simsbury, CT 06070 USA <br />�/ G ©2013 Veeder-Root Company • 576047-065 Rev. F • Printed in USA <br />TLS Capsule <br />Pressure <br />Sensor <br />i 1. Can only be used on wired installations. <br />s wlenclosure <br />i 2. Can only be used on wireless installations. <br />(Installation <br />' 3. Required when ordering 861190-201 sensor for wireless installations. <br />ISD <br />_ <br />t 1,4 1 Option 2) <br />i4. Only required for VST Vapor Processors. <br />Flowmeter <br />f t,9 t Wired or <br />} I , wireless <br />t <br />1 5. At least one seven channel module required when installing Carbon Canister Vapor <br />Polisher, optional on all other ISD sites. <br />_ e e <br />ISD Pressure Sensor <br />(Installation Option 1) <br />Wired only To learn more, contact us at 888.561.7942, or visit wwwveeder.com. <br />ilf I® ®C 125 Powder Forest Drive, PO. Box 2003, Simsbury, CT 06070 USA <br />�/ G ©2013 Veeder-Root Company • 576047-065 Rev. F • Printed in USA <br />