Laserfiche WebLink
3.5. TESTING A SINGLE-WALL MULTICOMPARTMENT TANK <br />WITH A SINGLE-WALL BULKHEAD <br />3.5.1. GENERAL <br />3.5.1.1. Remove all temporary service -fitting plugs. <br />3.5.1.2. Redope fittings and install plugs in all openings, except <br />one service fitting in each compartment (needed for the test <br />manifolds). Follow instructions in Point 3.1.5. (See FIGURE 3-6 <br />and FIGURE 3-7.) <br />3.5.1.3. Before doing the air test of the base tank (described in <br />SECTION 3.5.2.) and the air test of the end tank(s) (described in <br />SECTION 3.5.3.), install the test manifolds on the base and end <br />tank(s). <br />L fling Lug Typical Service Filbrg <br />Monitor Fitting <br />Types Manway with Fiftings When Double -Wall <br />Is Used <br />End Tank <br />Mfkhead <br />End Tank <br />Bulkhead �� '� \_ Flat <br />Seam for `'�� `- R <br />Seam for J Base Tank ` Seam for <br />End Tank End Tank <br />FIGURE 3-6 <br />Air Test of Base Tank <br />FIGURE 3-7 <br />FIGURE 3-8 <br />3.5.2. AIR TEST OF BASE TANK <br />3.5.2.1. Connect the pressure source to the test manifold on the <br />base tank. (See FIGURE 3-3 and FIGURE 3-7.) <br />3.5.2.2. Pressurize the base tank to 5 psig [3 psig for a 12 -foot - <br />diameter tank]. Allow the pressure to stabilize by adding or <br />removing air as necessary. <br />3.5.2.3. Close the air -supply valve on the test manifold in each <br />compartment. Disconnect the air -supply line. <br />3.5.2.4. Monitor the pressure for one hour. Do not release air <br />pressure. <br />11 <br />3.5.3. AIR TEST OF END TANK(S) <br />3.5.3.1. Connect the pressure source to the test manifold on the <br />end tank(s). (See FIGURE 3-3 and FIGURE 3-8.) <br />3.5.3.2. Pressurize the end tank(s) to 5 psig [3 psig for a <br />12 -foot -diameter tank]. Allow the pressure to stabilize by adding <br />or removing air as necessary. <br />3.5.3.3. Close the air -supply valve on the test manifold. <br />Disconnect the air -supply line. <br />3.5.4. EXTERNAL SOAP TEST <br />3.5.4.1. Soap the entire exterior of the tank, checking for leaks. <br />(Follow instructions in Points 3.1.6. through 3.1.8., including <br />Wamings following 3.1.8.) Watch for active air bubbles, which <br />indicate a leak. Pay special attention to fittings and manways. <br />3.5.4.2. Monitor the pressure for one hour. <br />3.5.4.3. After the test is completed, release all tank air pressure <br />and remove gauges. <br />3.5.4.4. Replace the protective covers in the service fittings. <br />3.6. TESTING A SINGLE-WALL MULTICOMPARTMENT TANK <br />WITH DOUBLE-WALL BULKHEAD(S) <br />Do not connect air supply directly to the interstitial -space <br />monitor fitting. Pressurizing the secondary tank (interstitial <br />space) by itself may damage the primary tank or cause tank <br />failure. <br />3.6.1. GENERAL <br />3.6.1.1. Remove all temporary service -fitting plugs. <br />3.6.1.2. Redope fittings and install plugs in all openings, except <br />one service fitting in each compartment (needed for the test <br />manifolds). Follow instructions in Point 3.1.5. (See FIGURE 3-6 <br />and FIGURE 3-7.) <br />3.6.1.3. Before doing the air test of the base tank (described in <br />SECTION 3.6.2.) and the air test of the end tank(s) (described in <br />SECTION 3.6.3.), install the test manifolds on the base and end <br />tank(s). <br />3.6.2. AIR TEST OF BASE TANK <br />3.6.2.1. Connect the pressure source to the test manifold on the <br />base tank. (See FIGURE 3-3 and FIGURE 3-7.) <br />3.6.2.2. Pressurize the base tank to 5 psig [3 psig for a 12 -foot - <br />diameter tank]. Allow the pressure to stabilize by adding or <br />removing air as necessary. <br />3.6.2.3. Close the air -supply valve on the test manifold on the <br />base tank. Disconnect the air -supply line. <br />3.6.2.4. Soap the fittings on top of the base tank to make sure fittings <br />are not leaking. Watch for active air bubbles, which indicate a leak. <br />3.6.2.5. Monitor the pressure for one hour. Do not release air <br />pressure. <br />