Laserfiche WebLink
3.7.2.5. Monitor the pressure for one hour. Do not release air <br />pressure. <br />3.7.3. AIR TEST OF END TANK(S) <br />3.7.3.1. Connect the pressure source to the test manifold on the <br />end tank(s). (See FIGURE 3-3 and FIGURE 3-12.) <br />3.7.3.2. Pressurize the end tank(s) to 5 psig. Allow the pressure <br />to stabilize by adding or removing air as necessary. <br />3.7.3.3. Close the air -supply valve on the test manifold on each <br />end tank. Disconnect the air -supply line. <br />3.7.3.4. Soap all service fittings and manways on the end <br />tank(s). Watch for active air bubbles, which indicate a leak. <br />3.7.3.5. Monitor the pressure for one hour. <br />3.7.4. AIR TEST OF SECONDARY TANK <br />3.7.4.1. Attach the quick -disconnect hose assembly from the <br />monitor fitting to the primary -tank service fitting (with a female <br />quick -disconnect fitting in place). This will allow air to transfer to <br />the interstitial space. (See FIGURE 3-4 and FIGURE 3-13.) <br />3.7.4.2. Add air as required and stabilize the air pressure in the <br />total tank system to 5 psig. <br />3.7.5. EXTERNAL SOAP TEST <br />3.7.5.1. Soap the entire exterior of the tank, checking for leaks. <br />(Follow instructions in Points 3.1.6. through 3.1.8., including <br />Warnings following 3.1.8.) Watch for active air bubbles, which <br />indicate a leak. Pay special attention to fittings and manways. <br />3.7.5.2. Monitor the pressure for one hour. <br />3.7.5.3. When the test is completed, carefully release the air <br />pressure from the tank by opening the air -supply valve. <br />3.7.5.4. When the airflow stops, remove the test manifold. <br />3.7.5.5. Replace the protective covers in the service fittings. <br />3.8. TESTING A DOUBLE-WALL MULTICOMPARTMENT <br />TANK WITH A WET INTERSTITIAL SPACE <br />CAUTION <br />Never pressurize a wet interstitial space. Doing so may <br />damage the primary tank or cause tank failure. <br />3.8.1. GENERAL <br />3.8.1.1. See FIGURE 3-10 for reference. <br />3.8.2. BASE TANK'S PRIMARY (INTERNAL) TANK <br />3.8.2.1. Keep the tank vertical (the reservoir on top) at all times <br />or the monitoring fluid may drain from the reservoir. <br />3.8.2.2. Remove all temporary service -fitting plugs and the <br />reservoir -fitting plug. <br />3.8.2.3. Check the monitoring -fluid level in the reservoir. It <br />should be about 1/4 full. <br />3.8.2.4. Visually check the interior of each compartment for <br />monitoring fluid. There should not be any. <br />n <br />3.8.2.5. Redope fittings and install plugs in all openings, except <br />one service fitting in each compartment (needed for the test <br />manifolds) and the reservoir fitting. Follow instructions in Point <br />3.1.5. (See FIGURE 3-6 and FIGURE 3-7.) <br />3.8.2.6. Before doing the air test of the base tank (described in <br />SECTION 3.8.3.) and the air test of the end tank(s) (described in <br />SECTION 3.8.4.), install a test manifold in the open service <br />fitting on both the base and end tank(s). <br />3.8.3. AIR TEST OF BASE TANK'S PRIMARY TANK <br />3.8.3.1. Connect the pressure source to the test manifold on the <br />base tank. (See FIGURE 3-3 and FIGURE 3-11.) <br />3.8.3.2. Pressurize the primary tank of the base tank to 5 psig. <br />Allow the pressure to stabilize by adding or removing air as <br />necessary. <br />3.8.3.3. Close the air -supply valve on the test manifold on the <br />base tank. Disconnect the air -supply line. <br />3.8.3.4. Soap all service fittings and manways. Watch for active <br />air bubbles, which indicate a leak. Look through the laminate for <br />any active air bubbles rising to the top. Their presence would <br />indicate an internal leak. Also, check the reservoir for bubbles in <br />the monitoring fluid. (The monitoring -fluid level will rise <br />during the air test.) <br />3.8.3.5. Monitor the pressure for one hour. Do not release air <br />pressure. <br />3.8.4. AIR TEST OF END TANK(S)' PRIMARY TANK(S) <br />3.8.4.1. Connect the pressure source to the test manifolds on <br />the end tank(s). (See FIGURE 3-3 and FIGURE 3-12.) <br />3.8.4.2. Pressurize the primary tank of the end tank(s) to 5 psig. Allow <br />the pressure to stabilize by adding or removing air as necessary. <br />Note: The monitoring -fluid level will rise during the air test. <br />3.8.4.3. Close the air -supply valve on the test manifolds on the <br />end tanks. Disconnect the air -supply line. <br />3.8.4.4. Soap all service fittings and manways. Watch for active <br />air bubbles, which indicate a leak. Check the reservoir for <br />bubbles in the monitor fluid. (The level of the monitor fluid will <br />naturally rise due to the pressure in the primary tank.) <br />3.8.4.5. Monitor the pressure for one hour. <br />3.8.4.6. When the test is complete, carefully release the air <br />pressure from all compartments by opening the air -supply valve. <br />3.8.4.7. When the air flow stops, remove the test manifolds. <br />3.8.4.8. Check the monitoring -fluid level in the reservoir. It <br />should be at approximately the same level as the pretest level. <br />3.8.5. SECONDARY TANK (EXTERNAL) <br />3.8.5.1. Check the exterior of the tank for monitoring fluid. (The <br />monitoring fluid is dyed blue to distinguish between moisture <br />and monitoring fluid.) If monitoring fluid is found, wipe the tank <br />dry and verify that the monitoring fluid does not reappear. Lift <br />the tank to check the bottom. Do not roll the tank. <br />A <br />