Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br />been addressed for SHELL k5 as of June 09, 2017. <br />Open violations from March 29, 2017 inspection <br />Violation #319 - No spill bucket, failed to contain five gallons, or failed to provide a means to keep it empty. <br />All USTs shall be equipped with a spill container that has a minimum capacity of five gallons and a drain valve that <br />allows drainage of the collected spill into the primary container or provide a means to keep the container empty. The <br />87 product spill container had a 3/8 inch drop in volume during the one hour hydrostatic annual test. Immediately <br />contact a properly licensed, trained, and certified contractor to correct the leak or replace with an approved spill <br />container under permit and inspection of the EHD. <br />The 91 product fill spill container failed to hold 5 gallons of liquid when tested. Technician measured about 700 ml of <br />water that could not be placed into spill container. The diesel product fill spill container failed to hold 5 gallons of <br />liquid when tested. Technician measured about 2400 ml of water that could not be placed into spill container. Spill <br />containers that do not have a 5 gallon capacity must be replaced once they fail a tightness test. <br />Page 1 of 1 <br />