My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2019
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
F
>
FRONTAGE
>
1022
>
2200 - Hazardous Waste Program
>
PR0519099
>
COMPLIANCE INFO_2019
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
6/30/2020 3:34:55 PM
Creation date
6/30/2020 3:21:39 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2200 - Hazardous Waste Program
File Section
COMPLIANCE INFO
FileName_PostFix
2019
RECORD_ID
PR0519099
PE
2229
FACILITY_ID
FA0014293
FACILITY_NAME
GILL EXPRESS INC
STREET_NUMBER
1022
Direction
E
STREET_NAME
FRONTAGE
STREET_TYPE
RD
City
RIPON
Zip
95366
APN
26102004
CURRENT_STATUS
01
SITE_LOCATION
1022 E FRONTAGE RD
P_LOCATION
05
P_DISTRICT
005
QC Status
Approved
Scanner
SJGOV\dsedra
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
67
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
STI Aboveground Storage Tank Visual Inspection Report Gill Express <br /> Inspector: Wesley Greenwood 1022 Frontage Road <br /> AST4 Ripon , California 95366 <br /> Date : November 26 2018 Used Oil <br /> Inspection Goal Methods Employed Results <br /> 7 . 2 DETERMINE ORIGINAL SHELL THICKNESS Unable to gain access to AST steel <br /> Plate surfaces . <br /> 721 1 Review original documentation . Not Available <br /> 7 . 2 . 2 Consult tank manufacturer. Consulted with AST manufacturer. <br /> 7 , 293 Examine tank labels for evidence of widely accepted UL 142 No. 31335 tag on AST, <br /> tank standard , such as Underwriters Laboratories Verified with the AST manufacture <br /> Standard UL142. AST UL 142 label is valid . <br /> 724 4 Measure shell thickness of several areas with no AST Shell Thickness Measurements <br /> corrosion Were Not Taken . <br /> 7 , 3 HORIZONTAL AST Requirements in addition to applicable items in 7 . 1 : <br /> 7 . 3 . 1 Inspect shell plates , Inspect areas accessible without entering AST. Not Applicable <br /> welds Concentrate where corrosion is likely . If significant <br /> internal corrosion is detected , further investigation <br /> using Ultrasonic Testing Scans UTS is required , <br /> 7 , 3 . 2 Inspect shell Inspect for changes made after AST was fabricated . Not Applicable <br /> attachments Record rapad^ eind/or insert plates . Inspect welds <br /> for si ns of stress and corrosion . <br /> 7 .4 VERTICAL or Requirements in addition to applicable items in 7 . 1 : Vertical, Fiberglass AST with a <br /> RECTANGULAR Fiberglass Top <br /> AST <br /> 7 . 4 . 1 Inspect shell plates , Inspect areas accessible without entering AST. Fiberglass Shell and Top were <br /> welds Concentrate where corrosion is likely. Thickness of Observed to be Free of Defects . <br /> each plate . If significant internal corrosion is <br /> detected , further investigation using UTS is required . <br /> 7 , 4 , 2 Inspect shell Inspect for changes made after AST was fabricated . No Modifications to the AST Were <br /> attachments Record repads and/or insert plates . Inspect welds Observed . All AST Appurtenances <br /> for signs of stress and corrosion . Were Observed to be Free of Leaks. <br /> 7 .4 . 3 Vertical AST Roof Inspect for low areas , standing water, paint failure, Not Applicable <br /> holes and corrosion. Take Ultrasonic Thickness <br /> Testing ( UTT) readings on roof and record results . <br /> If significant internal corrosion is detected , further <br /> investigation using UTS is required . <br /> P714 , 5 <br /> DOUBLE WALL & Requirements in addition to applicable items in 7 . 1 : Not Applicable <br /> DOUBLE BOTTOM <br /> AST <br /> Leak Detection Verify that the leak detection equipment method is Not Applicable <br /> o eratin if the tank is so a ui ed . <br /> . Inspect Interstice Check for leak or liquid in interstice, not vented to Not Applicable <br /> atmosphere . <br /> 7 , 4 , 7 Double bottom Double-bottom ASTs require UTT readings of areas Not Applicable <br /> that are single-wall . Double-wall ASTs do not require <br /> UTT readings ._ <br /> 7 . 5 INSULATED AST Requirements in addition to applicable items in 7 . 1 Not Applicable <br /> to 7.4 . <br /> 7 . 5 . 1 Remove insulation Remove insulation in areas where mold or moisture Not Applicable <br /> is present or likely to accumulate and examine metal <br /> surface for corrosion . <br /> 7 . 5 . 2 Verify damage If insulation damage is suspected , remove insulation Not Applicable <br /> extent until extent and nature of corrosion has been <br /> established . <br /> 7 . 5 . 3 Take LITT readings Take UTT readings on shell and record results. If Not Applicable <br /> significant corrosion is detected , further investigation <br /> using UTS is required . <br /> 7 . 5 . 6 FIELD ERECTED Additional requirements for field-erected ASTs are Not Applicable <br /> AST included in SP001 ATTACHMENT B . <br /> 7 . 7 FINAL REPORT include : Field data , measurements , pictures , Revised Final Report Dated <br /> drawings, tables and an inspection summary, December 15, 2018 Prepared , <br /> identify unacceptable conditions and recommended Visual Inspection Findings are <br /> corrective actions. Determine the suitability for Contained in the Final Report, <br /> continued service. Include the next scheduled formal <br /> external or internal inspection as applicable . Include <br /> inspector's name and certification number in report. <br /> i <br />
The URL can be used to link to this page
Your browser does not support the video tag.