Laserfiche WebLink
1. Describe how reusable medical waste carts or containers are cleaned and decontaminated(see below for <br /> approved cleaning methods): ® D :S. ra Ed <br /> Approved cleaning methods include agitation to remove visible soil combined with one of the following: <br /> 1. Exposure to hot water of at least 82 degrees Centigrade(180 degrees Fahrenheit)for minimum <br /> of 15 seconds. <br /> 2. Exposure to chemical sanitizer by rinsing with,or immersion in,one of the following for a <br /> minimum of three minutes: <br /> + Hypochlorite solution(500 ppm available chlorine) <br /> • Phenolic solution(500 ppm active agent) <br /> + Iodoform solution(100 ppm available iodine) <br /> + Quaternary ammonium solution(400 ppm active agent) <br /> m. Describe,if medical waste is treated onsite,a closure plan for the termination o t� atment,using at a <br /> minimum,one of the above referenced approved cleaning methods: <br /> I hereby certify to the best of my knowledge and belief that the statements made herein are correct and true. <br /> Printed Naive: °� _ I I `2 Signature: <br /> Title:_ C/i M IS` Date;— r <br /> EHD 45-03 8 <br /> 2015 <br />