Laserfiche WebLink
A 110 2nd Avenue South, #D7, Pacheco, CA 94553-5560 <br />McCampbell Analytical, Inc. Telephone: 925-798-1620 Fax:925-798-1622 <br />T' J Website: www.mccampbell.com E-mail: main@mccampbell.com <br />Matrix: S WorkOrder: 0402184 <br />EPA Method: <br />SW8015C Extraction: <br />SW3550C <br />BatchlD: 10354 <br />Spiked Sample ID: 0402175-002A <br />Sample <br />Spiked <br />MS* <br />MSD* <br />LCS <br />LCSD <br />CS-LCSD <br />Acceptance Criteria (%) <br />mg/Kg <br />mg/Kg <br />%Rec. % Rec.% <br />"-%/.RPDRec. <br />% Rec. <br />% RPD <br />LOW <br />High <br />TPH(d) <br />ND <br />150 <br />93.2 <br />94 <br />0.874 93.6 <br />95.4 <br />1.90 <br />70 <br />130 <br />%SS: <br />91.7 <br />50 <br />92.7 <br />93.3 <br />0.699 93.7 <br />95 <br />1.42 <br />70 <br />130 <br />All target compounds <br />NONE <br />in the Method Blank of this extraction batch were ND less than the method RL with the following exceptions: <br />= Matrix Spike; MSD = Matrix Spike Duplicate; LCS = Laboratory Control Sample; LCSD = Laboratory Control Sample Duplicate; RPD = <br />, Recovery = 100 * (MS -Sample) / (Amount Spiked); RPD = 100 * (MS - MSD) / ((MS + MSD) / 2). <br />MS and / or MSD spike recoveries may not be near 100% or the RPDs near 0% if: a) the sample is inhomogenous AND contains significant concentrations of <br />nalvte relative to the amount spiked, or b) if that specific sample matrix interferes with spike recovery. <br />IA = not enough sample to perform matrix spike and matrix spike duplicate. <br />R = analyte concentration in sample exceeds spike amount for soil matrix or exceeds 2x spike amount for water matrix or sample diluted due to high matrix or <br />DHS Certification No. 1644 IL— QA/QC Officer <br />