Laserfiche WebLink
Environmental Contractors <br /> FORWARD LANDFILL <br /> MONITORING DATA RECORDING FORM <br /> BLOWER/FLARE STATION 07202055.00 <br /> DATE: 03/16/2010 TECHNICIAN: Mricci <br /> TEMPERATURE: 66 BAR.PRESSURE: 30.26 <br /> WEATHER: Clear WIND DIRECTION: Northwest SPEED: 4 <br /> SECTION PRESS. I LFG - CH4 CO2 02 TEMP. BUTTERFLY <br /> (IN WC) FLOW % % % (°F) 'POSITION <br /> (SCFM) (%OPEN) <br /> VACUUM COCK -49.60 36.6 26.4 5.1 100 <br /> VALVE <br /> BLOWER INLET -49.60 90 100 <br /> BLOWER OUTLET 3.80 1,108 87 100 <br /> PRESSURE COCK <br /> VALVE 36.1 26.0 5.3 <br /> INSTRUMENT READINGS AND OTHER OBSERVATIONS <br /> BLOWER IN OPERATION: 2 PILOT LINE PRESSURE(PSIG): 10.0 <br /> 1: 15,941 hours 29.8 amps PROPANE TANK LEVEL(%FULL): 50 <br /> 2: 13,844 hours 29.8 amps SPARE PROP.TANK LEVEL(%FULL): 100 <br /> BLOWER BEARING TEMP.(F): DAMPER POSITION: %OPEN 50 <br /> #1 INLET: 86 DISC.: 152 INLET PRESSURE@ FLAME ARRESTOR: <br /> #2 INLET: 82 DISC.: 107 3.8 <br /> BLOWER KO DELTA P(IN WC): FLAME ARRESTOR DELTA P(IN WC): <br /> FLARE EXIT GAS TEMP(°F) TANK LEVEL(INCHES): 5.0 <br /> ACTUAL: 1,583 AIR COMPRESSOR(PSI): 180.0 <br /> SET: 1,600 AIR COMPRESSOR HOURS: <br /> FLOW METER(SCFM): 1,108 CONDENSATE METER(GALLONS): 136,310 <br /> VFD SET POINT: MONTHLY READING AT CARBON DRUM <br /> VFD FLOW(%): (PPM): <br /> OTHER MAINTENANCE OR MONITORING,PERFORMED <br /> DO FLARE ARRESTERS REQUIRE CLEANING: No <br /> DO FILTERS REQUIRE CHANGING: No <br /> DIALER PHONE LINE VERIFIED FOR OPERATION: Yes <br /> DIALER PROGRAMING VERIFIED: On <br /> BACK UP FLARE TESTED MONTHLY,DATE OF TEST: <br />