Ms. Erin Fanning <br /> June 30, 2014 <br /> Page 2 <br /> 40 <br /> Gas monitoring well testing procedures are as follows: <br /> • Connect sample tubing, open test valve; observe pressure and record data. <br /> • For probes 20 feet deep or less,turn on sample pump, observe and record methane, <br /> oxygen, and carbon dioxide gas concentrations,when readings have stabilized for 30 <br /> seconds. <br /> • For probes more than 20 feet deep,turn on sample pump,extract a minimum of one <br /> probe volume,observed and record methane,oxygen,and carbon dioxide gas <br /> concentrations,when readings have stabilized for 30 seconds. <br /> • Close test valve, disconnect sample instruments and secure sample location. <br /> SCS monitored structures by testing random selected locations where methane gas would most <br /> likely accumulate(e.g.,electric outlets and junction boxes, conduits, drains, cabinets and closets). <br /> Other required monitoring documentation(e.g., sampling personnel, date,time and meteorological <br /> conditions) is shown on the attached testing data tables. <br /> GAS MONITORING PROBE TESTING <br /> In accordance with the approved testing schedule, all perimeter compliance GP probes are to be <br /> tested at a minimum,on a quarterly basis. On April 2, May 1, 8 and 14,and June 9, 2014, all <br /> accessible perimeter Gas Monitoring Probes defined as GP-01 through GP-28R were tested for <br /> the presence of LFG. <br /> Test results (Table 1) indicated that all GP probes tested exhibited methane gas concentrations <br /> below the LEL (5 percent by volume) or no methane gas was detected. These results indicated <br /> that as of the date of this report, the subject site perimeter probes are in compliance with the <br /> requirements of Title 27 CCR Article 6. <br /> SCS is scheduled to perform third quarterly monitoring of 2014 (July through September) of the <br /> GP probes by the end of the month of September 2014, or more frequently as directed by RSI. <br /> ON -SITE INTERIOR STRUCTURE TESTING <br /> In accordance with the approved testing schedule,the interiors of on-site structures are to be tested <br /> at a minimum, on a quarterly basis. On June 24, 2014, on-site structures(i.e., landfill office, <br /> portable office, scale house, locker room and supply room) were tested for the presence of methane <br /> gas. In each structure, random selected locations (i.e., electrical outlets and junction boxes, <br /> conduits, drains, floor cracks, etc.)were tested. Test results(Table 2) indicated no methane gas <br /> was detected at any accessible location tested. <br />