Laserfiche WebLink
L.7 <br />Citation No, 03-10.07C-004 <br />NCYCC <br />Page 5 <br />1 <br />2 As seen from the PGE detections in the table above, Well No. 4 produces the water with <br />3 the lowest levels of PCE and should be utilized as the system's lead well. Well No. 1 <br />has the second lowest PCE concentrations and should have mechanical repairs <br />5 completed as soon as possible so that the well can be monitored and utilized to <br />6 supplement the lead Well No. 4 if Well No. 1 remains in compliance with all MCLs. Well <br />,T No, 2 should be used as little as possible until treatment has been installed, and <br />8 Standby Well No. 3 is to be used only for short term emergencies with public <br />9 notification. <br />10 <br />11 <br />12 <br />13 Due to the violation of the Tetrachloroethylene MCL during the month of March 2007, <br />14 NCYCC is hereby directed to take the following actions: <br />15 <br />16 1, In accordance with Section 64463 of Title 22, California Code of Regulations <br />1.7 (22CCR), NCYCC is required to notify the consumers of the institution of the <br />1a Tetrachloroethylene MCL exceedence. Exceeding chemical MCLs is a Tier 2 <br />19 violation22CCR Section 64463.4 , which requires ( } q providing public notice to <br />20 persons served as soon as practical but within 30 days after the water system is <br />21 <br />made aware of the violation. <br />22 <br />23 <br />24 <br />25 <br />2s <br />r� <br />COURT PAPER <br />S'"ATC or C&Llro RNJA <br />STB I{3 IREV- 0.7z, <br />85 34709 q. <br />a. This notification shall be given in English. In addition, each notice must <br />contain information in Spanish regarding > 1) the importance of the notice <br />or (2) contain a telephone number or address where Spanish speaking <br />consumers may contact the water system to obtain a translated copy of <br />the public notice or assistance in Spanish. ',F <br />