Laserfiche WebLink
• <br />L� <br />DEL -TECH DEL -TECH GEOTECHNICAL SUPPORT SERVICES <br />(209) 847-8757 (OFFICE) - (209) 847-7744 (FAX) - deltechl@pacbell.net (Email) <br />SITE: FORWARD LANDFILL / MANTECA, CA. <br />AUSTIN & FORWARD MONTHLY MONITORING LOG 2015 <br />GROUNDWATER TREATMENT FACILITY- PUMPING SYSTEM & AIR STRIPPER <br />SYSTEM PH. # 209.234.8499 / 555 CALL RESPOND CODE <br />DATE dune 16,2015 <br />TIME 15:00 <br />LOCATION EW - 1 <br />EW -2 <br />EW- 3 R <br />EW- 4 <br />TOWER <br />AUSTIN <br />FORWARD <br />SYSTEM ON LINE <br />METER # 08-08679-03 <br />08-08678-03 <br />08-08680-03 <br />09-00773-03 <br />09-05971-04 <br />TOWER AIR <br />PRESSURE <br />( inches H20) <br />38.0 <br />FREEBOARD ft. <br />FREEBOARD ft. <br />TOTALIZER 4,442,050 <br />N/A <br />7,732,570 <br />7,006,340 <br />65,042,400 <br />3.5 <br />4.0 <br />POWER METER NONE <br />N/A <br />62,551 <br />NONE <br />32,618 <br />SYSTEM FLOW <br />( GPM) 5.0 <br />0.0 <br />55.0 <br />50.0 <br />110.0 <br />IftEUENI <br />PRESSUREPST 1 5.0 <br />0.0 <br />80.0 <br />37.0 <br />20.0 <br />T. <br />rTAXL DEP 100' <br />118' <br />113' <br />115' <br />EW- 1 <br />w <br />SAMPLE EFFLUENT <br />PH 7.42 <br />EW -2 <br />N/A <br />EW -3R <br />6.94 <br />EW- 4 <br />I <br />7.40 <br />TOWER <br />IN / OUT <br />7.40 8.29 <br />PONDS <br />AUSTIN <br />9.05 <br />FORWARD <br />10.04 <br />E.C. 406 <br />N/A <br />900 <br />395 <br />600 <br />574 <br />9,105 <br />20,030 <br />TEMP. 18.8 <br />N/A <br />21.0 <br />20.8 <br />22.8 <br />22.8 <br />31.4 <br />30.0 <br />O.R.P. 77 <br />N/A <br />88 <br />82 <br />90 <br />90 <br />31 <br />184 <br />T.D.S ( PPM) 275 <br />N/A <br />624 <br />265 <br />406 <br />388 <br />7,479 <br />18,380 <br />TURBIDITY 1 <br />N/A <br />2 <br />2 <br />2 <br />2 <br />12 <br />10 <br />COLOR CLEAR <br />CLEAR <br />CLEAR <br />CLEAR <br />CLEAR <br />SIGNED:�� �a <br />EW -2 OFFLINE / PUMP MOTOR HAS FAILED. REPLACED MOTOR CONTROL AND ANALYZER. PUMP MOTOR NEEDS TO BE REPLACED. <br />