Laserfiche WebLink
State of California California Environmental <br /> Protection Agency <br /> MEMORANDUM <br /> To: Scott Walker Date: , <br /> Closure and Remediation Branch =' <br /> From: `G - <br /> Timothy W Crist, P.E. <br /> Closure and Remediation Branch <br /> CALIFORNIA INTEGRATED WASTE MANAGEMENT BOARD <br /> Subject: HARNEY LANE SANITARY LANDFILL - GAS CONTROL SYSTEM <br /> FACILITY FILE: 39-AA-0003 <br /> Documents Reviewed <br /> • Technical Specifications for Landfill Gas Control <br /> System Construction for Harney Lane Sanitary Landfill, <br /> San Joaquin County, California, EMCON Associates, <br /> March 1994 . <br /> • Contract Plans - Harney Lane Sanitary Landfill Gas <br /> Control System, San Joaquin County, California, EMCON <br /> Associates, March 1994 . <br /> Comments - Technical Specification <br /> 1 . Section 01730-Installation , Operation, and Maintenance <br /> Instructions - This section should contain system start-up <br /> instructions for: <br /> • adjusting gas extraction wells to maximize the <br /> extraction of landfill decomposition gas to prevent <br /> off-site gas migration and she minimize the influx on <br /> ambient air which can lead to fires in the buried <br /> waste. <br /> • performing influence testing of the gas extraction <br /> wells, especially those nearest occupied structures, to <br /> insure that the influence zones of each well overlap <br /> sufficiently to prevent off-site gas migration. <br /> 2 . Section 0221-3 .4 .0 Dewateripq This section should have <br /> wording to the effect that all water which comes into <br /> contact with buried waste is to be considered leachate and <br /> handling as any other leachate on the site. <br />