Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8 . SUMP/ UDC TEST <br /> Test Method Developed by © Manufacturer © Industry Standard Professional Engineer <br /> Test Type © Pressure © Vacuum ❑fT Hydrostatic <br /> Test Equipment Used : <br /> Sump/ UDC ID 87 STP 89 STP 91 STP UDC 1 -2 <br /> Sump Manufacturer Unknown Unknown Unknown Bravo <br /> Sump Depth ( inches) 42 43 44 10 <br /> Sump Bottom to Top of 6 7 7 Bottom <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 09 : 37 10 : 29 10 : 29 11 : 31 <br /> Initial Reading 3 . 3102 1 . 2410 1 . 5437 1 . 5324 <br /> Test End Time 09 : 52 10 : 44 10 : 44 11 : 46 <br /> Final Reading 3 . 3102 1 . 2392 1 . 5432 1 . 5322 <br /> Change in Reading 0 -0 . 0018 - 0 . 0005 - 0 . 0002 <br /> Pass/ Fail Criteria +/- 0 . 002 +/- 0 . 002 +/- 0 . 002 +/- 0 . 002 <br /> Tightness Test Results © Pass ® Fail ® Pass rl Fail © Pass r] Fail ® Pass © Fail <br /> Sump/ UDC ID UDC 34 <br /> Sump Manufacturer Bravo <br /> Sump Depth ( inches) 10 <br /> Sump Bottom to Top of Bottom <br /> Highest Pipe Penetration <br /> ( inches) <br /> Test Start Time 11 : 31 <br /> Initial Reading 1 . 0344 <br /> Test End Time 11 : 46 <br /> Final Reading 1 . 0340 <br /> Change in Reading -0 . 0004 <br /> Pass/ Fail Criteria +/- 0 . 002 <br /> Tightness Test Results Pass Fail Pass Fail r] Pass © Fail LM Pass Ln Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section . <br /> Page 3 of 5 <br />