Laserfiche WebLink
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ORLANDOS 1 18754 E HWY 26 , LINDEN July 21, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> r306 <br /> Remarks <br /> HSC 25291(e)Water in secondary containment not removed, analyzed, and properly disposed of(pre-Jul 2003). <br /> OBSERVATION: Liquid was observed in the UDC 7/8. <br /> REGULATION GUIDANCE: If water could enter into the secondary containment by precipitation or infiltration, it <br /> must be removed and disposed of properly. <br /> CORRECTIVE ACTION: Immediately remove this liquid, make a hazardous waste determination per Title 22 <br /> hazardous waste regulations, and manage it accordingly. Ensure that all sumps and annular spaces are maintained <br /> free of liquid. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> An inspection checklist was provided to the facility operator on the day of the monitoring system certification <br /> inspection (07/21/2020).The EHD has completed the paperwork inspection report on 12/24/2020 which <br /> replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 01/23/2021. <br /> To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br /> of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br /> ($152). To schedule an appointment, please call (209) 468-3420. <br /> Documents provided: Return to compliance certification form, corrective action statement form and a schedule <br /> of CUPA free training classes. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: <br /> Date: December 24, 2020 Inspector: Inspector Phone: <br /> Printed Name and Title: PAUL NSO, EH Specialist (209) 616-3049 <br /> E Mailed report, <br /> FA0007722 PR0507164 SCO01 07/21/2020 <br /> EHD 23-01 Rev.9/16/2020 Page 5 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />