Laserfiche WebLink
Hazardous Waste Tank System June <br /> Written Assessment per CCR Title 22 <br /> Zoom Car Wash 4661 Quail Lakes Dr. Stockton CA 95207 2019 <br /> Tank Assessment Page Tank Name/marking: Used Antifreeze <br /> Tank <br /> Tank age: 11 years, estimated <br /> Manufacturer: unknown <br /> Remaining service life: 25 years, inspect <br /> in 5 years <br /> Tank Construction: <br /> Shape: Cylindrical Closed Top, Flat Bottom, Single Wall <br /> Orientation: Vertical <br /> Location (above/below ground): Above ground <br /> Material of construction: HDPE <br /> Thickness and method Waste to determine: 0.21" by UTG <br /> Lining material & thickness (if applicable): N A. <br /> Corrosion Protection equipment: Compatible <br /> Structural support: The tank rests on concrete foundation. <br /> Other identifying features: Natural White <br /> Piping and ancillary equipment (pumps): NA, Gravity <br /> Piping Material of Construction: Steel <br /> Piping Diameter: 1" <br /> Pump location(s): NA <br /> Pump type(s)/capacities: NA <br /> Overfill Protection: none <br /> Material Storage: <br /> Material and characteristics: Waste Antifreeze, Toxic <br /> Specific Gravity: 1.05 <br /> Operating Capacity: 182 gallons <br /> Strandberg Associates 1(866) 388-0404 john@strandbergassociates.com 13 <br />