Laserfiche WebLink
CSIL E C H 1 m irc}om ental l Laboratories <br /> {},-,1 t KI%Wk1 an', A%LMIL ll,ii,wiE iint I l{, <br /> 141cp1onc (�Q) 272-'_700 1 1v (-)o2) w-"78L) <br /> I <br /> QA/QC Report <br /> Method <br /> szsoB <br /> Matrix Water <br /> Date Analyzed 3116106 <br /> IDate Extracted 3116106 <br />' Perimeters Conc ug/L Spike Recove % Control Limits RPD <br /> MS MSD Added MS MSD Roc RPD <br /> 1,1-Dichloroethene 60 53 50 120 106 70--130 20 14 <br />' Benzene 52 50 50 104 100 70-130 20 4 <br /> Trichloroethene 53 49 50 106 98 70-130 20 8 <br /> Toluene 5652 50 1 112 104 70-130 20 8 <br /> Chlorobenzene 56 54 50 1 112 108 70-130 20 4 <br /> m,p-X lenes 127 119 100 1 127 119 70-130 20 8 <br /> . MS Matrix Spike <br /> MSD Matrix Spike Duplicate <br /> RPD Relative Percent Difference of MS and MSD <br /> Perimeters Method Units Det <br /> Blank Limit <br /> 1,1-Dichloroethene ND u /L 1 <br /> Benzene ND ug/L 0 5 <br /> Trichloroethene ND u /L 0 5 <br /> Toluene ND ug/L 0 5 <br /> Chlorobenzene ND u /L 0 5 <br /> m, -X lenes ND u /L 0 6 <br /> MTBE ND u /L 1 <br /> TBA ND u /L 10 <br /> DIPE ND u /L 1 <br /> ETBE ND u IL 1 <br /> TAME ND u /L 1 <br /> 1,2-DEchloroethane ND u /L 0 5 <br /> EDB ND ug lL 0 5 <br /> Ethylbenzene ND u /L 0 5 <br /> o-Xylene ND uq/L 06 <br /> TCE N❑ u /L 1 <br /> PCE ND u IL 1 <br /> I <br /> 1f) f 11 Il I)! f)f( SII I) 10 1 ti1E)NII KtiAIIS \ € €ON <br />