Laserfiche WebLink
CASTLE ANALYTICAL LABORATORY <br /> Environmental Testing Services 2333 Shuttle Drive,Atwater,CA 95301 Phone (209)384-2930 <br /> Certificate#2079 Fax (209)384-1507 <br /> Advanced GeoEnwronmental Inc Client Project ID Top Filling Sampled 6-21-00 <br />' of Northern Caldorn:a Reference Number 3064 Received 6-22-00 <br /> 4005 North Wilson Way Sample Description Water Extracted 6-22-00 <br /> Stockton CA 95205 Sample Prep/Analysis Method EPA 503018015, 8020 Analyzed 6-22-00 <br /> Attn Tim Cuellar Lab Numbers 3064-1W 2W 3W,4W, 5W Reported 6-28-00 <br />' TOTAL PETROLEUM HYDROCARBONS -GASOLINE <br /> WITH BTEX DISTINCTION <br />' ANALYTE REPORTING LIMIT SAMPLE 1D SAMPLE ID SAMPLE ID SAMPLE ID SAMPLE ID <br /> MW- 1 MW-2 MW-3 MW-4 MW-5 <br /> 6-21-00 6-21-00 6-21-00 6-21-00 6-21-00 <br /> (ug/L) (ug/L) (ug/L) (ug/L) (ug/L) (ug/L) <br /> MTBE 050 NO NO 100 NO NO <br />' BENZENE 050 NO - 28 770 NO 46 <br /> TOLUENE 050 NO NO 48 NO ND <br /> ETHYL BENZENE 050 NO 25 44 NO 110 <br /> TOTAL XYLENES 050 NO 59 80 ND 130 <br /> I GASOLINE RANGE <br /> HYDROCARBONS 50 NO 170 1800 NO 2000 <br /> Report Limit Multiplication Factor 1 1 20 1 10 <br /> Surrogate %Recovery FED 101/,1 PID 1026 FID 104%1P0 1446 FID 103%1PID 1036 FID Be9%1 PID 9a 2% FID 142%1RID 965% <br /> instrument ID VAR-GC1 VAR-GC1 VAR-GC1 VAR-GC1 VAR-GC1 <br /> Analytes reported as NO were not detected or below the Practical Quantitation Limit <br /> Practical Quantitation Limit= Reporting Limit x Report Limit Multiplication Factor <br /> ANALYST APPROVED BY <br /> Clar J one Ja C 7yhiffips <br /> nvironmental Lab Director <br />