Laserfiche WebLink
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Pilot Travel Center Lathrop- 1017 345 Roth Rd, FRENCH CAMP August 25, 2020 <br /> Other Violations <br /> 2010 1 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 103 HSC 25292.2, 25299.30 Failure to submit and maintain complete and current financial responsibility documents. <br /> OBSERVATION: The Current financial responsibility documents were not found on site. <br /> REGULATION GUIDANCE: A copy of current financial responsibility documents are required to be maintained on <br /> site. <br /> CORRECTIVE ACTION: Immediately obtain a copy of the facility's financial responsibility documents and maintain a <br /> copy on site. <br /> This is a minor violation. <br /> 124 CCR 2637.2(d&e), 2665(a&b)"Overfill Prevention Equipment Inspection Report Form" not submitted within 30 days <br /> of inspection. <br /> OBSERVATION: Overfill prevention testing was performed on 07/22/2020. A test report has not been submitted to <br /> the EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE: A copy of the 'Overfill prevention Testing Report Form' must be submitted within 30 <br /> days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> This is a minor violation. <br /> 313 HSC 25290.1, 25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight. <br /> OBSERVATION: Leaking meter was observed in UDC 1/2 and small amount of liquid was observed in UDC 9/10, <br /> indicating a leak in the primary containment. <br /> REGULATION GUIDANCE: All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION: Immediately have a properly licensed, trained, and certified contractor repair or replace the <br /> failed component(s), under permit and inspection of the EHD if necessary. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> The monitoring system certification was conducted on 8/25/2020 and the paperwork inspection completed <br /> today(9/10/2020).An inspection checklist was provided to the facility operator on the day of inspection. The <br /> EHD has written the complete report which replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification Form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 10/10/2020 <br /> FA0023459 PR0540987 SCO01 08/25/2020 <br /> EHD 23-01 Rev.8/11/2020 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />