Client:
<br /> OIL/ WATER SEPARATOR INSTALLATION NOTES CATHODIC PROTECTION NOTES �7 ^
<br /> 1 . OWS TANKS MUST BE INSTALLED ACCORDING TO OWS MANUFACTURER INSTALLATION INSTRUCTIONS, 1 . ALL BLACK STEEL PIPE & FITTINGS IN CONTACT WITH THE GROUND ARE TO BE WRAPPED FLYING J TRAVEL CENTER
<br /> (PUB NO INST 8001), AND NFPA 30 AND 31, AND/ OR COATED FOR CATHODIC PROTECTION PER SPECIFICATIONS.
<br /> 2. THE EXCAVATION SHALL BE FREE FROM MATERIAL THAT MAY CAUSE DAMAGE TO THE #618
<br /> OW MATTER ISNNOT,
<br /> INTRRODUCED INTO THE TAKEN
<br /> INSTALLATION
<br /> TM) SHOULDMYDAMAGE OCCUR 1501 N JACK TONE RD',
<br /> CONTRACTORIS TO CONTACT OWNER REPRESENTATIVE IMMEDtATELY, OIL WATER SEPARATOR GENERAL NOTES RIPON, CA 95336
<br /> 3. THE BOTTOM OF THE EXCAVATION SHALL BE COVERED WITH CLEAN BACKFILL TO A DEPTH OF 1 . GENERAL TANK SPECIFICATIONS:
<br /> ONE FOOT MINIMUM AND GRADED LEVEL
<br /> 4, THE EXCAVATION SHALL EXTEND A DISTANCE OF 24" MINIMUM AROUND THE PERIMETER —SINGLE—WALL FIBERGLASS OIL/WATER SEPARATOR,
<br /> OF THE TANK AND ABIDE BY OSHA STANDARDS. —NOMINAL CAPACITY OF THE SEPARATOR CHAMBERS IS 4,000 GALLONS
<br /> TOTAL CAPACITY: 4,000,
<br /> 5, A PRE—INSTALLATION AIR TEST OF THE SEPARATOR ABOVE GROUND IS REWIRED. —OIL STORAGE CAPACITY IS 380 GALLONS. LOCATOR MAP SANTOSAVE
<br /> PRESSURE SFIALL NOT EXCEED 5 POUNDS PER SQUARE INCH (PSIG) WHILE A S064P SOLUTION —SPILL CAPACITY IS 2,400 GALLONS..
<br /> IS APPLIED TO ENTIRE TANK SURFACE AND ALL FITTINGS, ADDITIONALLY INSPECT OWS DITEMOR —ESTIMATED WEIGHT OF TANK IS 4,000 Abs.
<br /> FOR DAMAGE UPON DEANERY, REMOVE THE MAN WAY COVER PLATES) AND INSPECT THE —DESIGNED FLOW RATE IS 146 GPM. a,, ,,mP9u�LL - -
<br /> INTERIOR TO INSURE THAT ALL BAFFLESAND INTERNAL PIPING ARE SECURE AND HAVE NOT —REMOVABLE POLYPROPYLENE CWLE'SCER PLATE PACKS ARE INSTALLED. _ S
<br /> TANK TESTING PRESSURE IS 5 PSIG MAXIMUM. - 0
<br /> 6, EQUIPMENT TO UFT THE SEPARATOR SHALL BE OF ADEQUATE SME TO UFT AND LOWER THE —DEADMEN WITH (2) HOt.D—DOWN STRAPS ME PROVIDED 8Y MANUFACTURER,
<br /> 0
<br /> BEEN DAMAGED DURING TRANSPORT. —
<br /> SEPARATOR WTDKtUT DRAGGING OR DROPPING TO ENSURE NO DAMAGE TO THE SEPARATOR, 1
<br /> 7. SEPARATOR SHALL BE CAREFULLY LIFTED AND LOWERED BY USE OF CABLES OR OWNS OF
<br /> ADEQUATE LENGTH (NOT MORE THAN 50 DEGREE INCLUDED ANGLE) AND ATTACHED TO THE 1
<br /> LIFTING LUGS PROVIDED, A SPREADER BAR SHOULD BE USED WHERE NECESSARY. UNDER
<br /> NO CIRCUMSTANCES ARE THE USE OF CHINS OR SONGS AROUND THE SEPARATOR SHELL
<br /> ALLOWED.
<br /> 8. THE SEPARATOR MUSE BE INSTALLED IN A LEVEL AND PLUMB POSRION, CHECK ELEVATIONS •• • ! • ! •'
<br /> AT EACH END OF THE SEPARATOR WITH A TRANSIT AND ADJUST AS NECESSARY TO 1/2" IN QTY EQUIPMENT SCHEDULE - - • •
<br /> 20'-0". CHECK ELEVATIONS ACROSS THE DIAMETER OF THE SEPARATOR AND ADJUST TO Q
<br /> 1/4' IN 1D'—D'. XERXES 633454.07 - 4,000 GALLON, 610 X 21,,11" LONG, SINGLE WALL FIBERGLASS
<br /> 9. SPECIAL CARE SHOULD BE EXERCISED WHEN INSTALLING THE HOLD DOWN, MACE SURE THAT UNDERGROUND OIL/WATER SEPARATOR WITH 22" X 30"H MANWAY W (2) 4" NPT FTGS AND • • •I••
<br /> DEAD MEN SECTIONS HAVE AT LEAST TWO ANCHOR POINTS, FOLLOW OWS MANUFACTURERS 1 (2) 48" X 6" CONTAINMENT COLLAR OMTEC—OWI-2 TANK LEVEL MONITOR PROBE (2) HOLD
<br /> INSTRUCTIONS FOR DEAD MEN ANCHORING, ALL EXPOSED STEEL HOOKS, WIRE, ETC., TO BE DOWN STRAPS. DEADMENT SUPPLIED WITH TANK. OWS - NOTES / EQUIPEMENT
<br /> COATED FOR CATHODIC PROTECTION.
<br /> 10, APPROVED BACKFILL MATERIAL CONSISTING OF PEA GRAVEL OR CRUSHED STONE, SHALL BE 2 OPW 23-0033, 2" OPEN VENT
<br /> PLACED 12" HIGH ALONG BOTTOM SIDES OF SEPARATOR BY HAND SHOVELING AND PROBING
<br /> TO ENSURE PROPER SUPPORT BENEATH TANK BOTTOM, REPEAT PROCEDURE WITH ANOTHER OPW CONQUISTADOR 39CD—WT18, 391/4" BOLT-DOWN COMPOSITE MANWAY COVER ASSY W
<br /> 12" LIFT AND THEN COMPLETE BACKFILLING TO THE TOP OF TANK, 1 18" SKIRT
<br /> Ila FILL SEPARATOR WITH CLEAN WATER TO BALLAST, AFTER BALUSTNG IS COMPLETE CHECK
<br /> ELEVATIONS FOR PROPER TOLERANCES. CLOSE VALVES OF INLET AND OUTLET PIPES UNTIL NEF - NEF-STP—PT—NC, 48" X 36" HIGH FIBERGLASS CONTAIMENT SUMP EXT W 32" SUMP
<br /> THE DRAINAGE AREA IS PAVED' 1 OPENING AND WATERTIGHT UD AND MULTISIDED49" FIBERGLASS CONTAINMENT SUMP W
<br /> 12, WHERE AIR OR HYDROSTATIC TESTING IS REQUIRED AFTER INSTALLATION, IT IS RECOMMENDED 30" H X 20" W VERTICAL FLAT PANELS. CUT AS REQUIRED,
<br /> THAT THE PRESSURE APPLIED SHALL NOT BE IN EXCESS OF 5 POUNDS PER SQUARE INCH
<br /> (PSIG) AS MEASURED AT THE TDP OF THE SEPARATOR 1 OMTECH 2" NPT BRASS BUSHING (AT LEVEL MONITOR RISER)
<br /> 13, EXTEND ALL VENT LINES TO ATMOSPHERE AS SHOWN, SEPARATOR MUST BE VENTED TO
<br /> ASSURE PROPER OPERATION, EXTEND RISERS TO A MINIMUM OF 12'-0" ABOVE FINISHED 1 MORRISON 184 SERIES 2500 MB 4" X 2" X To DOUBLE TAP BUSHING (AT LEVEL MONITOR RISER)
<br /> GRADE
<br /> 14, THE THREAD PROTECTORS OF UNUSED OPENINGS SHALL BE REMOVED, PERMANENT METALBLACK STEEL PIPE AND FITTINGS (FOR LEVEL MONITOR AND VENT RISERS) TO BE FURNSHED
<br /> PLUGS TREATED WITH PIPE COMPOUND SHALL BE INSTALLED AT ALL UNUSED OPENINGS. ASST AND INSTALLED BY CONTRACTOR,
<br /> 15. TOP OFF SEPARATOR WITH CLEAN WATER UNTIL WATER IS DISCHARGED FROM OUTLET PIPING, SCHEDULE 40 PVC PIPE AND FITTINGS (FOR OIL WATER SEPARATOR INFLUENT AND EFFLUENT
<br /> THE SEPARATOR MUST BE FULL OF WATER TO OPERATE VENT PLUGS MUST BE REMOVED ASST CONNECTIONS AND CLEANOUT CONNECTIONS) TO BE FURNISHED AND INSTALLED BY
<br /> FOR SEPARATOR TO FILL
<br /> CONTRACTOR
<br /> 16. NO "PERNCO" TYPE FITTINGS ALLOWED AT ANY PART OF THE OWS PIPING SYSTEM. ALL
<br /> CONNECTIONS TO BE MECHANICAL OR SOLVENT/ CEMENT TYPE
<br /> 17 BEFORE BACK FLUNG THE CONTRACTOR SHALL VIDEO TAPEF DRAINAGE PIPING INSTALLATION OWS MANHOLE/SUMP SCHEDULE
<br /> & OIL/ WATER SEPARATOR INSTA ATION CONTRACTOR IS ALSO RESPONSIBLE FOR PROVIDING
<br /> THF OWNER REPRESENTATIVE ( ONSTR 1 TION MANAGER OR PROJECT MANAGER). AS—BUILT LOCATION SME MANUF. MODEL N0, EXTENSION SUMP N0,
<br /> DRAWINGS AND THE VIDEO TAPE OF THE PRODUCT PIPING & TANK INSTALLATION.® INLET PIPE WITH VENT 36NO RIVERSIDE 1063SX10DA HDPE
<br /> ® 24" MANWAY EXTENSION 39 1/2*0 DPW 39CD—WT18 NEFNEF—STP—PT—NC Job #: FJ -616-OWS
<br /> ® LEVEL SENSOR AND STICK RISER 24L OPW 6110-2410 HDPE
<br /> ® OUTLET PIPE WITH VENT 36"f RIVERSIDE 1063SX10DA HDPE 13.7
<br /> ® _+ Revisl0nr ,
<br /> DISCHARGE CLEANOUT 18"! RIVERSIDE 10618X10 HDPE �� )O NE SCOVEYGROUP, INC.
<br /> 9595 Loos Ranch Rd. N100
<br /> Rancho Cummorga, CA 91730
<br /> Office: INS) 972-7561
<br /> Cumtat Ucense 8604431
<br /> Dass: AB HAZ