Laserfiche WebLink
TAI T <br /> ■14r0 TO iMt Cw����r01 701 N.Pa,kcente Dave,Santa Ana.CA 92705 <br /> p:714/560/8222 www.tait.com <br /> Identification of Test Procedures for Secondary Containment Testing <br /> To Whom It May Concern: <br /> Tait Environmental Services, Inc., utilizes the following procedures when conducting Secondary <br /> Containment Testing: <br /> 1) Containment Sumps,Transition Sumps, UDCs—Tait follows PEI-RP1200-17 Section 6.6 for the <br /> accelerated test method.Tait uses the Incon TS-1000 hydrostatic test equipment following the <br /> attached procedures. <br /> 2) Spill Buckets; Direct Bury&Contained in Sumps—Spill buckets contained in sumps are tested <br /> per PEI-1200-17, Section 6.2, however Tait Pass/Fail threshold is 0" drop in one hour. Direct Bury <br /> Spill Buckets are test the same as containment sumps per PEI-1200-17,Section 6.6. <br /> 3) Tank Annular Space—testing is conducted per PEI-1200-17, Section 4.2 <br /> 4) Piping Secondary Containment—Testing is conducted per PEI-RP1200-17,Section 5.3 <br /> Please consider this letter as our Test Procedure utilized when conducting Secondary Containment <br /> Testing in lieu of either parts or the whole RP1200 document due to copyright infringement. <br />