Laserfiche WebLink
SWRCB,January 2006 <br /> Spill Bucket Testing Report Form <br /> This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and <br /> printouts from tests(if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. <br /> 1.FACILITY INFORMATION <br /> Facility Name:7-ELEVEN#32262,MKT 2368(N-3940-1 Date of Testing:3/3/2020 <br /> Facility Address:2360 W GRANTLINE I-205 OFF RAMP,TRACY,CA 95376 <br /> Facility Contact:CHANDRA Phone:209-830-9917 <br /> Date Local Agency Was Notified of Testing:2/18/2020 <br /> Name of Local Agency Inspector(ifpresent during testing):UNKNOWN tj <br /> 2.TESTING CONTRACTOR INFORMATION MAR U 5 2029 <br /> Company Natne:TANKNOLOGY INC. <br /> Technician Conducting Test:Jesus Saldivar " MENTAL HEA <br /> Credentials): r CSLB Contractor W ICC Service Tech. r— Tank Tester r' Other(Specify) pARTMENT <br /> License Number(s): <br /> 3.SPILL BUCKET TESTING INFORMATION <br /> Test Method Used By: r Hydrostatic r Vacuum r Other <br /> Test Equipment Used:LAKE TEST Equipment Resolution:0.0625 in. <br /> Spill Box#Tank T4 RUL Spill Box#Tank T5 MUL Spill Box#Tank T6 PUL <br /> Identify Spill Bucket(By Tank REG UNLEAD-Fill 1- M[DGRADE-Fill I-Direct PREMIUM-Fill 1-Direct- Spill Box# <br /> Number, Stored Product, etc.) Direct-Grade level in -Grade level in Grade level in containment <br /> containment sump containment sump sump <br /> !' Direct Bury r Direct Bury r Direct Bury f Direct Bury <br /> Bucket Installation Type: (? Contained in Sump C• Contained in Sump Contained in Sump f Contained in Sump <br /> Bucket Diameter: 12.00 12.00 12.00 <br /> Bucket Depth: 16.50 15.00 13.00 <br /> Wait time between applying <br /> 5 min 5 min 5 min min <br /> vacuum/water and start of test <br /> Test Start Time(Tl): 07:45:00 07:45:00 07:45:00 <br /> Initial Reading(Rl): 16.00 in.H2O 15.00 in.H2O 13.00 in.H2O <br /> Test End Time(TF): 08:45:00 08:45:00 08:45:00 <br /> Final Reading(RF): 16.00 in.H2O 15.00 in.H2O 13.00 in.H2O <br /> Test Duration(TF—Tl): 1 hr I hr 1 hr <br /> Change in Reading(RF—Rl): 0.00 in.H2O 0.00 in.H2O 0.00 in.H2O <br /> Pass/Fail Threshold or Criteria: +/-0.00 +/-0.00 +/-0.00 +/- <br /> Test Result: Pass Pass Pass <br /> Comments-(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING <br /> I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. <br /> Technician's Signature: /.J&— Date: 3/3/2020 <br /> 'State laws and regulations do not currently require testing to be performed by a qualified contractor.However,local requirements may be more stringent. <br /> WO:2344236 <br />