Laserfiche WebLink
S0 JOA U 1 Environmental Health Department <br /> U ;� i I <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> CHEVRON#208117** 755 S TRACY BLVD,TRACY February 06, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 319 CCR 2635, 2637.1,2665, 2712 No spill bucket,failed to contain 5 gallons, no means to keep it empty, or failed to be <br /> tested. <br /> OBSERVATION: The 87 product spill container failed when tested. <br /> REGULATION GUIDANCE:All USTs shall be equipped with a spill container that collects any hazardous <br /> substances spilled during delivery operations,that has a minimum capacity of five gallons and a drain valve that <br /> allows drainage of the collected spill into the primary container or provide a means to keep the container empty. <br /> CORRECTIVE ACTION: The drain valve in spill container was replaced and retested during the inspection. <br /> This was corrected on site. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by 3/7/2020. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209)468-3420. <br /> Documents provided during inspection: <br /> -EHD class schedule <br /> -Return to compliance certification <br /> -Corrective Action Statement <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: February 06, 2020 Inspector: Inspector Phone: <br /> ' Printed Name and Title: SHEWIT WOLDEAREGAY, EH Specialist (209)468-0216 <br /> Teena Townsell, Manager <br /> FA0007938 PR0508090 SCO01 02/06/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 4 of 4 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />