Laserfiche WebLink
Environmental Health Department <br />Facility Name and Address: FAIRWAY WEST CONDOMINIUM ASSN, 6724 PLYMOUTH RD, STOCKTON 95207 <br />Swimming Pool Official Inspection Report <br /> #37 Electrical Hazards <br />OBSERVATIONS: The GFI breaker for the functioning pool light needs to be replaced as it does not turn off the pool light <br />when tripped. Pool light must remain off and pool must be closed before dark. Repair both lights so there is adequate light <br />for the pool. <br />CALCODE DESCRIPTION: Electrical equipment installed in the water, walls, deck, or equipment room of a public pool shall comply with <br />California Electrical Code. (CEC 680.4) Light fixtures installed in the pool that operate at more than 15 volts shall be protected by a ground <br />fault circuit interrupter. (CBC 3160B) <br />OVERALL INSPECTION NOTES AND COMMENTS <br />OBSERVATIONS <br />Flow rate:gpm <br />pH: <br />Chlorine:ppm <br />Cyanuric acid:ppm <br />Temp:º F 80 <br />7.2 <br />1.4 <br />0.0 Combined chlorine:ppm0.4 <br />NOTES <br />Influent Pressure: 12 psi <br />Effluent Pressure: 12 psi <br />The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br />Safety Code. If a reinspection is required, fees will be assessed at the current hourly rate. <br />Received by: Name and Title: <br />EH Specialist:Phone:(209) 468-3442 <br />Cole, Paragon Pools <br />AARON GOODERHAM <br />Page 2 of 2EHD 36-01 Rev. 06/30/15 Swimming Pool OIR <br />FA0002525 PR0360042 SC001 08/02/2018 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjcehd.com