San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone: (209)468-3420 Fax: (209) 468-3433 Web:www.sjgov.orq/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Pilot Travel Center Lathrop- 1017 345 Roth Rd Lathrop August 23 2018 <br /> UST System Observations <br /> 319 CCR 2635(b) No spill bucket,failed to contain five gallons,or failed to provide a means to keep it empty ❑V ❑R ❑COS <br /> 320 CCR 2635(b)(2) Overfill prevention system not present or failed to meet overfill requirements ❑V ❑R ❑COS <br /> 321 CCR 2635(b)(2) Overfill prevention was overridden ❑V ❑R ❑COS <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status ❑V ❑R ❑COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status ❑V ❑R ❑COS <br /> 324 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V ❑R ❑COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored ❑V ❑R ❑COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 329 HSC 25298 Failed to comply with all permanent closure requirements ❑V ❑R o COS <br /> 330 CCR 2636(f)(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system ❑V ❑R ❑COS <br /> 331 CCR 2630(d) Secondarily contained piping not maintained to allow liquid to drain into sump ❑V ❑R ❑COS <br /> 332 CCR 2631(b),2631(d) Primary and/or secondary containment not constructed in accordance with the established standards ❑V ❑R ❑COS <br /> Single-Walled Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS ll,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 105 CCR 2632(d)(1), 2634(d) Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the EHD. The plans for both tanks incorrectly state the leak <br /> detectors are VMI LD 3000. The leak detectors observed on site are VMI 99 LD 2000. The monitoring plan must be <br /> uploaded to the California Environmental Reporting System (CERS). Immediately log into CERS, make the necessary <br /> changes, and submit for review by the EHD. <br /> This is a minor violation. <br /> 301 HSC 25292.1 UST system is not operated to prevent unauthorized release, including spills and overfills. <br /> The fuel filters under the dispensers are not located to allow drips and leaks to drain back into the UDC. The <br /> underground storage tank system shall be operated to prevent unauthorized releases. Immediately provide approved <br /> secondary containment for the filters under permit and inspection by the EHD. <br /> This is a Class II violation. <br /> FA0023459 PR0540987 SCO01 08/23/2018 <br /> EHD 23-01 Rev.09/22/16 Page 3 of 4 Underground Storage Tank Program OIR <br />