Laserfiche WebLink
Table A-12a. Facility L - Pulp Mill <br /> Source Description <br /> Facility Name, Port Townsend Paper Company <br /> Location: Port Townsend, WA <br /> Facility Type: Kraft Pulp Mill <br /> Source Type: Power Boiler, No. 10. 200,000 lb/hr steam <br /> Test Dates: February 25 and March 5, 1986 <br /> Other fuel(s): Hogged fuel, oil <br /> Air pollution control 600 tube multiclone followed by venturi scrubber. <br /> device(s) used: Multiclone operated at 3.5 - 4 inch HZO pressure differential. <br /> Venturi operated at 15 inches H20when tires burned and 13 <br /> inches when tires were not burned. Venturi water rate <br /> 2,500 - 2,900 gpm. <br /> Test Conditions: Approximately 7% TDF by heat input <br /> Test Methods: Washington DOE Methods 3 and 5 <br /> Fuel Shredded tires <br /> Handling/Feeding: <br /> Testing Company: Washington DOE <br /> Environmental Washington DOE <br /> Agency: <br /> Reference: State of Washington (1986e) <br /> Source Test Data Evaluation <br /> Yes No Unknown <br /> Data Expressed in Emission Factor Form X <br /> Baseline Fuel Test Data Available X <br /> Accurate Fuel Feed Rates X <br /> Multiple Baseline Fuels X <br /> Test Witnessed by or Prepared for <br /> Governmental Agency X <br /> A-32 <br />