Recommended Practices for the Testing and Verification of Spill,Overfill,Leak Detection and Secondary Containment Equipment at UST Facilities <br /> Verify that the console has no active or <br /> recurring history of leak detection-related <br /> warnings or alarms. In the event of any <br /> such warnings or alarms, notify the appro- <br /> priate person before continuing the test. <br /> Where possible print out the system setup <br /> and any alarm histories from the console. <br /> Save the printout for facility records or = <br /> make an electronic copy. ` <br /> 8.2.1.5 Test Equipment. Test equip- <br /> ment shall include: <br /> • tools for the removal of the ATG probe <br /> and sensors; <br /> • tape measure or gauge stick; <br /> • water-finding paste. <br /> 8.2.1.6 Test Procedure. <br /> 1. Measure the product and water level <br /> in the tank and compare to the console <br /> readings to confirm ATG accuracy. If <br /> the readings do not agree, contact the FIGURE 8-2. When removing and replacing the ATG <br /> appropriate erson. s <br /> P probe, be careful to avoid damaging any of the compo- <br /> 2. Remove the ATG probe cap and nents. <br /> disconnect the cable from the ATG. 3 <br /> 9. Clear the alarm conditions. <br /> 3. Remove the ATG probe from the tank. <br /> 10. For the water float, slowly move the <br /> Use care to ensure that the floats on <br /> the stem do not catch on the bottom float up the probe until the water <br /> of the riser during removal. alarm is triggered. <br /> s <br /> 4. Inspect the probe. The floats must u• Measure the distance from the bottom <br /> move freely on the stem without of the probe to the water float when <br /> binding. If any parts are damaged the float first triggers the water alarm. <br /> or missing, contact the appropriate 12. Compare the measurements for prod- <br /> person. uct float and the water float in Steps 8 <br /> and 11 to the values programmed into N <br /> S. Reconnect the probe cable. the console. <br /> 6. Set the fuel float in the middle of the <br /> probe and verify that it is showing the 8.2.1.7 Pass/Fail Criteria. If the mea- <br /> correct inch reading on the console. surements for the product and water floats <br /> match the values programmed in the con- <br /> 7. Slowly move the fuel float up the sole and the console acknowledges the 3 <br /> probe until the high product alarm is high product and water level alarms, the <br /> triggered on the console. If the system ATG probe passes the test. <br /> does not alarm at the pre-set level, <br /> contact the appropriate person. If the measurements for the product and <br /> S. Measure the distance from the bottom water floats do not match the values pro- <br /> of the probe to the fuel float when the grammed in the console or the console <br /> float first triggers the high product does not acknowledge the high product <br /> alarm or water level alarms, the ATG probe fails <br /> the test. <br /> pei.org <br />