The following is an itemized list of aboveground petroleum storage act violations that <br /> have not been addressed for MCLANE FOODSERVICE DISTRIBUTION as of July <br /> 23, 2020. <br /> Open violations from January 09, 2019 inspection <br /> Violation#711 -Failed to perform scheduled tank tests or inspections by appropriately qualified personnel. <br /> The two 15,000 gallon diesel tanks were not tested on schedule by qualified personnel. The SPCC plan calls for a <br /> certified STI SP-001 integrity inspection"as soon as possible"since the tanks could not be dated. The SPCC plan <br /> or the inspection checklists in th eSPCC plan do not address the inspection of interstitial space of double walled <br /> tanks, as required by SP-001 inspection checklists. Each aboveground container shall be tested and inspected for <br /> integrity on a regular schedule and whenever repairs are made. The qualifications of personnel performing tests <br /> and inspections, frequency and type of testing and inspections that take into account container size, configuration, <br /> and design shall be determined in accordance with industry standards. Examples of these integrity tests include, <br /> but are not limited to: visual inspection, hydrostatic testing, radiographic testing, ultrasonic testing, acoustic <br /> emissions testing, or other systems of non-destructive testing. Comparison records and other records of <br /> inspections and tests must be maintained on site. Immediately conduct the necessary testing and submit a copy of <br /> the test results to the EHD, or provide equivalence as allowed by CFR 112.7(a)(2). <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Page 1 of 1 <br />