Laserfiche WebLink
Facility Name: Costco # 1031 Manteca (Page 4) <br /> I. Results of Vacuum/Pressure Monitoring Equipment Testing <br /> Manufacturer: Veeder-Root Model : 332117-001 System Type: ❑ Pressure ®Vacuum <br /> Sensor <br /> ID <br /> s9 Component(s) Monitored by this Sensor: 87a Product Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> s10 Component(s) Monitored by this Sensor: 87a Vapor Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> s11 Component(s) Monitored by this Sensor: 87a Vent Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> s12 Component(s) Monitored by this Sensor: 87b Product Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> s13 Component(s) Monitored by this Sensor: 87b Syphon Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> s14 Component(s) Monitored by this Sensor: 87b Vent Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> s17 Component(s) Monitored by this Sensor: 91 Product Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> s18 Component(s) Monitored by this Sensor: 91 Vent Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> 519 Component(s) Monitored by this Sensor: Additive Product Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> 520 Component(s) Monitored by this Sensor: Additive Vent Line <br /> Sensor Functionality Test Results: ® Pass; ❑ Fail Interstitial Communication Test Result: ® Pass: ❑ Fail <br /> How was interstitial communication verified? <br /> ® Leak Introduced at Far End of Interstitial Space; ❑ Gauge; ❑ Visual Inspection; Other (Describe in J below) <br /> Vacuum was restored to operating levels in all interstitial spaces: ® Yes ❑ No (if no, describe in J below) <br /> J. Comments: In dispenser 5-6 there is no loss of vacuum when doing the comunication <br /> testing. Someone will need to come out and figure out why there is no vacuum loss when <br /> the ball valve to the secondary vacuum under the product line os opened. It works in all <br /> dispensers except dispenser 5-6. <br />