Alarm is "ON" , self 1. Turn both equal. pumps' switches on <br /> priming centrifugal the elect. panel to the "MAN" position <br /> pump does not operate. 2 . If the pump operates OK, check the <br /> electrical circuit from the Kari float <br /> switch to the circuit breaker for <br /> discontinuity. <br /> 3 . If the pump does not operate, check the <br /> equal. pump's fuse and circuit breaker <br /> in the electrical panel. <br /> 4 . If the fuse and circuit breaker are <br /> OK, replace the pump for repair. <br /> Alarm is not "ON" 1. Make sure the main power switch on the <br /> electrical panel is in the "ON" <br /> position. <br /> 2 . If there is no electrical power, check <br /> from the source to the elect. panel . <br /> 3 . If there is electrical power, check <br /> the electrical circuit of the Kari <br /> float switch for discontinuity. <br /> 4 . If the Kari float switch is OK, check <br /> the fuse and electrical circuit on <br /> the electrical panel . <br /> 5 . If the Kari float switch is not OK, <br /> replace if necessary. <br />